2.3 ENTRY BY CON EDISON PERSONNEL
NOT QUALIFIED FOR ELECTRICAL WORK,
CONTRACTORS, OR PUBLIC IMPROVE- MENT PERSONNEL
If entry takes place immediately after the initial
inspection, a follow-up inspection is not required
provided that the Con Edison inspector or the
contractor foreman were on location during the initial inspection by the qualified electrical worker. If entry by non-qualified personnel (i.e., Con Edison
employees not qualified for electrical work, and
contractors) is not immediate but takes place within 72 hours of the initial inspection, a “follow-up
inspection” shall be conducted prior to each entry.
The follow-up inspection shall be conducted by a qualified person (Con Edison or contractor trained by Con Edison) involved in the work and include:
Verification that the initial inspection was
performed in the specified time frame.
Testing for stray voltage by a qualified
Con Edison employee or qualified contractor.
Completion of atmospheric testing as outlined in Chapter 1.
Determination that it is safe to enter the space.
A visual inspection for abnormalities such as faults or non-capped cable.
Communication of inspection results and
hazards to the con Edison inspectors and the contractor foreman.