Page 11 - DualMIST DIOM
P. 11

    f) Maximum Distances from Columns
 Reference
If nozzles are installed closer than 600mm from one side of a column, another nozzle shall be installed on the opposite side of the column within:
  2750mm
 2500mm
 2000mm
DM3
DM4R
DM4C
ww w. dualmist.
DM5
g) Minimum Flow Rates , Pressure & K Factor
2500mm
     Reference Minimum Flow Rate Minimum Pressure K Factor
65 LPM
50 LPM
60 LPM
5 Bar
5 Bar
5 Bar
6 Bar
29
22
27
20
    DM3
DM4R
DM4C
ww w. dualmist.
DM5
50 LPM
              www.dualmist.com
11