OLH Output high limit Range:
rnP
Control output maximum rate of rise
- From 0 to 100 % when device is configured with one control output.
- From -100 to 100% when device is configured with two control outputs.
This parameter is available only when Pb is different from zero
It is programmable from 1% to 25% of the output per second.
tOL Time duration of the output power limiter (soft start)
Above the 25%/s, the display will show "InF" meaning that no ramp is imposed.
Range: from 1 to 540 min.Above this value the display shows “InF” meaning that the limiting action is always on Note: The tOL can be modified but the new value will become operative only at the next instrument start up.
Hbd Threshold value for out 1 break down alarm
This parameter is available only when P10 is equal to N.O. or N.C.
Range: From 0 to P11 value (in ampere). Notes:
The threshold resolution will be equal to 0.1 A for range up to 20 A and 1 A for range up to 100 A.
The hysteresis of this alarm is fixed to 1% of fsv
SCA Threshold value for OUT 1 short circuit alarm.
This parameter is available only when P10 is equal to N.O. or N.C.
Range: From 0 to P11 value (in ampere).
Notes:
The threshold resolution will be equal to 0.1 A for range up to 20 A and 1 A for range up to 100 A.
The hysteresis of this alarm is fixed to 1% of fsv