Page 50 - Engineering in Kenya Mag
P. 50
of the absorption. The models depended on inputs that include the location (longitude and latitude), the solar day of the year, the direct global solar radiation GB, and diffuse solar radiation GD. GB was obtained from satellite data showing the solar irradiance in Nairobi (Table 1)
Table 1: Solar insolation values for Nairobi
1The average monthly direct global solar radiation GB on a tilted surface measuring 1m2 was 849 W (Table 14).
Parameters
Values
Units
Solar radiation values
Average Monthly Direct Global Solar Radiation (GB)
849
W/ m2
Average diffuse radiation on horizontal surface (GD)
208
W/ m2
Total Collector Area (AC)
3
m2
Direct Beam radiation on tilted surface (GBt) (without considering absorptance -transmisivity)
1016
W/m2
Diffuse beam radiation on tilted surface (GDt) (without considering absorptance -transmisivity)
299
W/m2
Ground reflected radiation on tilted surface (GGt) (without considering absorptance -transmisivity)
42
W/m2
Total radiation falling on FPC (Gt)without considering Absorptance - transmisivity of the FPC-Isotropic model
1357
W/m2
Final Absorbed radiation by FPC (Gt) including Absorptance - transmisivity of the FPC-Isotropic model
1065
W/m2
Considering an average of 8 hours of sunshine per day, this translates to approximately 6.79kWh/m2/day. The results were consistent with the current literature. A Study by Wasike (2015) demonstrates that three areas in Kenya had monthly insolation levels on a horizontal surface of about 6.5 to 7.0 kWh/m2/day between January and March. This reduced to 4.8 kWh/m2/ day in May and further downwards to 4 kWh/m2/day from June-July, attributable to the considerable cloud cover (Wasike, 2015)2. The results are also similar to those obtained by Hille et al. (2011).
Total energy transferred to adsorption system
The thermal energy collected by the FPC is transferred to the adsorption system. Assuming a collector efficiency (F’) of 0.8, and the average heat absorbed by the collector per square meter, Qnet = 813.668 W; the total energy transferred to the water into the storage tank, was calculated as:
Number and Size of FPC Required for a Three Bedroom House
The model also evaluated as a case study; the number of flat plate collectors needed to cool a normal three-
bedroom residential house. In the model, it was assumed that a standard three-bedroom house has a kitchen, living room, one en-suite bedroom and two standard bedrooms. The estimated cooling load for the case study house was found to be 6.265 kW. Assuming that the adsorption cooler supplies all this energy, then, the air conditioner must supply a cooling load of 6.265kW. Since the adsorption system has a COP of 0.3, then, the total cooling load is:
Each solar collector of size 1m2 supplies 658 W of heat. To correctly match the demand, the total area that should be occupied by the collectors is:
Discussion
Evaluating the practicability of the system
From the model, the total size of FPC’s required is 32m2; if each collector has an area of 2 square meters, a total of 16 FPC’s will be required. For this study, it is assumed that the three-bedroom house has a gable roof with medium pitch (6/12 or a rise of 6 inches for every 12-inch horizontal), and a further assumption is made that the roof does not have a complex design. Furthermore, it is assumed that the roof runs parallel to the long side of the building. With these estimates, the total roof area is approximately 118.22m2,
Engineering in Kenya Magazine Issue 2
48