Page 36 - Designing for Zero Carbon - Case Studies of All-Electric Buildings
P. 36

CASE STUDY NO. 1
SANTA MONICA CITY HALL EAST
   Energy Design Analysis and Energy Performance:
Modeling versus Post-Occupancy Measurements
Energy Use — Modeling
Energy modeling was done for the parametric studies of design alternatives as well as for the final design. IES Virtual Environment9 was used for these design studies and for the documen- tation required as part of the Living Building Challenge certification. Energy Pro was used to demonstrate code compliance.
Since the building is designed to operate largely in natural ventilation mode, the actual air flow through the spaces was modeled using Ansys Fluent10 software, which uses computational fluid dynamics (CFD) analysis to predict actual patterns of air movement under different exterior con- ditions. This software was also used to simulate the radiant floor/ceiling system fluid flows in order to provide estimates of the amount of heat transfer into and out of the concrete slabs.
As noted above, the energy modeling was effective in assisting with the proper sizing of the solar PV system so that the requirements of the Living Building Challenge could be met. Charts show- ing the modeled annual and monthly energy use by category of load (heating, cooling, lighting and equipment) are shown on the following pages.
Energy Use — Actual Measurement and Comparison to Modeling Results
The building’s original opening day (Earth Day 2020) coincided with the mandated shutdown of public buildings due to the Covid-19 pandemic. The building’s energy use for 2020-2021 there- fore has not been representative of the normal operation with full staff and general public access. Furthermore, the new building and the historic City Hall are on the same public utility meter. A separate submeter has been installed on the new building, which will record each category of energy use when it is fully integrated into the BMS. This is necessary for the Living Building Challenge certification and is expected to complete its first year of measured data collection of energy use in 2022.
Energy Production versus Energy Use: Zero Net Energy
The roof-mounted solar PV system was installed and activated in June 2020, followed by the canopy-mounted system in October 2020. There was a drop in recorded output in April 2021 caused by the inverters being offline when the system was being integrated into the BMS, but otherwise the system has been producing electric power as planned. Much of this energy was put into the public utility grid until June 2021, when the building finally opened to the public and some partial occupancy commenced.
The solar PV system performance for the first full year of operation (October 2020 – September 2021), as atypical and somewhat sporadic during startup as it was, is shown in the chart on page 24, Solar Photovoltaic System Performance. For reference, the modeled energy use is shown on the same chart. As required for the Living Building Challenge performance data submittal, actual energy use will replace this modeled reference data in the future.
The second chart on page 24, Cumulative Net Energy Performance, sums the net energy pro- duction each month to that of the month prior, so that the annual total would be exactly zero if the performance is zero-net-energy (ZNE). The chart shows that this building is in fact net positive.