Page 110 - PBL614 IM/SM500F-EN SM500F ( WIRO)
P. 110

SM500F
Field mountable paperless recorder 7 Configuration
Select the totalizer action following a power failure and a digital signal to stop and start the totalizer:
Stop/Go recovery
Last – On power recovery, the totalizer continues in the same state as before the failure, i.e. stopped or running.
Stop – Totalizer stops counting.
Go – Totalizer starts counting from the last recorded value.
Stop/Go source
Select a signal source to stop and start the totalizer; refer to Appendix A, page 146 for a description of the available sources.
Note. This signal is edge-triggered. A rising edge (inactive to active) starts the totalizer. A falling edge (active to inactive) stops the totalizer.
Select a 'Reset source' signal (see Appendix A, page 146) – an edge-triggered signal to reset the totalizer on a rising edge.
Set the 'Preset count' value – the value the totalizer counts from and the value applied when the totalizer is reset.
Set the 'Predetermined count' value – the value at which the totalizer stops or wraps.
Note.
 A counter configured to count up must have a 'Preset count' value lower than the 'Predetermined count' value. A counter configured to count down must have a 'Preset count' value greater than the 'Predetermined count' value.
 Set the required number of decimal places on the higher of the 'Preset count' value or 'Predetermined count' value.
Set the 'Intermediate count' value – the value at which a digital source is activated. This can be used as an alarm threshold to indicate when the 'Predetermined count' value is about to be reached.
       􏰬􏰇􏰈􏰪􏰇
    􏰬􏰇􏰋􏰂