Field mountable paperless recorder Appendix E – Math Equations
E.4 Logarithmic Scales
When 'Scale Type' is set to 'Log' (see page 95), the Chart view's scale bar and graduations are displayed in logarithmic format with the input signal plotted linearly on the chart:
The recorded value in the Chart and Indicator views is driven by the engineering range selected and displayed in exponential format:
Chart View Indicator View
Example
An application requires a 4 to 20 mA input signal with an associated engineering range of 0 to 1,000,000 to be displayed in exponential format and plotted on a logarithmic chart with a scale of 1 to 10+6.
1. Referring to page 95:
a. Set 'Scale Type' to 'Log'
b. Set 'Low' to '1'
c. Set 'High' to '1.0E+6'
2. Referring to page 97:
a. Set Engineering range 'Low' to '0'
b. Set Engineering range 'High' to '6'
c. Select Engineering Units as required
In this configuration, the input is plotted linearly on the chart but the digital indicator displays the input in exponential (logarithmic) format in order to match the logarithmic scale displayed on the chart.
         Note. The logarithmic value of the input is obtained by displaying '10 to the power of the engineering range value'. Therefore, in the case of 0 to 1,000,000, the engineering range must be set to 0 to 6 as 10+6 = 1,000,000.
     Note. Regardless of the scale type setting:
 All alarms on the recording channel are triggered by the channel's linear value.
 Data values saved to the archive files are the linear output from the recording channel.