Page 110 - Sterilization Training Manual
P. 110
ANALOG OUTPUT ADJUSTMENT
To SEC a zero reading is 4.00 milliamps +/- 0.05 milliamps (mA).
To SEC a span reading is 12.00 milliamps +/- 0.05 milliamps (mA).
Some customers have very sophisticated high resolution sterilizer control systems. In order to compensate for the control system readings or wiring loss the SEC device should be able to be “tweaked” to closely match the control system readings.