4.8.4 Relay Module Device Coil Assignments Screen
1) The Top Information Panel is identical to the description previously, for the Relay Module Device Summary Screen.
2) The middle section of the screen displays the coil assignments for the coil number titled (for this example, it is coil #3).
3) It shows the source assigned (on the left) for the trigger action (on the right). The source may be a specific SEC 3100 device, a specific zone, or the global loop status.
4) The source assigned is used by the Boolean logic function established by the trigger panel to the right. It can be any combination of the four alarm conditions. A trigger remains active until a higher trigger becomes active (i.e. {example not shown above} If “Low Alarm” is only selected above, then when the Gas Level rises above the Low Alarm and causes the trigger to activate; and as the gas rises above the low alarm, the trigger will stay active until it reaches the mid alarm level- and since the mid alarm is NOT selected as a trigger in this example, the trigger becomes in-active until the gas level falls into its range.).
5) The trigger Boolean function result is then applied to the settings for how to engage the coil itself. If the “Polarity” above is set to normally de-energized (N.DEN.), then an active trigger will cause the coil to become energized, otherwise it will be de- energized.