Page 7 - Gas Detection Systems Training Manual
P. 7

I. SPECIFICATIONS
Model: SEC 3000 Gas Detector Model Number: SEC3000
Available gases:
Ammonia
Nitric Oxide Bromine
Fluorine
Hydrogen Chloride Hydrogen Sulfide Arsine
Hydrogen Selenide Formaldehyde
Please note that this list is not all-inclusive. The SEC 3000 sensors can be calibrated for other toxic gases provided a calibration gas is available. For more please contact Sensor Electronics Corporation.
Carbon Monoxide Hydrogen Oxygen Phosgene
Chlorine
Hydrogen Peroxide
Hydrogen Cyanide
Nitrogen Dioxide
Diborane Germane Phosphine Silane
Detection Method: Electrochemical or Galvanic
Aspiration:
Diffusion
Optional Sample Draw (requires 1 liter per minute sample flow rate)
Output (Analog): 4-20 mA (Source type), max. 1000 Ohm load at 24 VDC supply voltage Output (Digital) Interactive Interface Available On The Calibration (White) Wire Response Time: Varies for type of sensing element
Construction: 316 Stainless Steel Explosion Proof
Accuracy: +/- 5%
Operating Temperature Rating:
-40 to +50C at 0 to 99% RH (non-condensing) Operating Voltage:
8 to 32 VDC measured at the detector head Power Consumption: 1 Watt Max.
Max. Current Draw: 40 mA (at 24 VDC)
Chlorine Dioxide Ozone Hydrogen Fluoride Sulfur Dioxide
Approvals:
Explosion Proof Intrinsically Safe
CSA c,us: Class I, Division 1, Groups B,C,D IECEx CSA 13.00xx: Ex d IIB+H2 T4 Gb
T6
Imax Pmax Ci
CSAc,us: Cl I, Division 1, Groups ABCD CD
Vmax 10.4V 16.4V
148mA 1.2W 148mA 1.2W 148mA 1.2W
Li 2.51uF 22.5uH
2.51uF 22.5uH 2.51uF 22.5uH
T-Code T4 T4
T4
D IECEx CSA 13.00xx: Ex ia IIC T4 Ga
InstallationCategory: Cat.I,PollutionDegree2
Doc#: 1460003, Rev A Operation Manual, SEC 3000 Electro-Chemical Gas Sensor
Page 4 of 13
26.3V


































































































   5   6   7   8   9