ELX SERIES
          30” STANDARD ALSO AVAILABLE 24” HIGH
              54” MINIMUM. DIMENSION VARIES WITH DEPTH OF THE EQUIPMENT.
LIGHT FIXTURE
CONTINUOUS HANGING BRACKET
SUPERCAPTURETM LIP
6’-8” MTG. HT.
*16’ -0” MAX. UNIT LENGTH.
FOR GREATER LENGTH, JOIN TWO OR MORE SECTIONS TOGETHER. ALLOW 12” MIN. OVERHANG AT EACH END.
   12” MIN.
10” OR 12”
GAYLORD BALANCING DAMPER (LISTED)
“XGS” SUPER HIGH EFFICIENCY FILTRATION EXTRACTOR
12” MIN.
             0.5 GALLON GREASE CUP
              Mechanical Requirements
ENGINEERING DATA
The amount of exhaust volume required is dependent upon the type of cooking equipment and the type and volume of cooking. Contact factory for exhaust vol- umes, duct sizes, and static pressures.
Electrical
Provide 208-250VAC, 50/60 Hz, Single Phase, 20 amp service for every 2 ventilator sections to power UVi lamps. Ventilator lights to be on separate circuit, 120 volt 50/60Hz standard, 220/240 volt optional.
Ventilator Lengths
Maximum unit length 16’-0”. For greater lengths, join two or more sections together. Check to ensure that there is adequate access into building and kitchen area. *Note: Ventilators manufactured outside North America; maximum unit length 10’-0”.
Hanging Weight
Ventilator Width Wt. / Lineal Ft.
54” 60” 66”
Lbs. 125 130 135
  Form No. ELX-UVi-BBC-CL 1218-20198 © Copyright 2018, Gaylord Industries
Litho USA
“AUTOSTART” SENSOR
RTD SENSOR