Page 86 - Gaylor Blue Book
P. 86
EXHAUST
CFM
DUCT SIZE STATIC PRESSURE
VH2 Type II Hood
PROJECT NAME: ______________
ITEM NO.:____________________
MODEL "VH2" SERIES
TYPE II VAPOR HOOD
• MODEL VH2-W (WALL MOUNT)
• MODEL VH2-I (ISLAND STYLE)
OPTIONS
• • •
100 WATT INCANDESCENT LIGHT LED PUCK LIGHT
SLIDING BALANCING DAMPER
The manufacturer reserves the right to modify the materials and specifications resulting from a continuing program of product improvement or the availability of new materials
Form No. VH2 -30723 032020
© Copyright 2020, Gaylord Industries
Litho USA
Model "VH2"
Determining Exhaust Volumes
APPLICATION
Dishwasher
Dishwasher
Light Duty Cooking
Light Duty Cooking
WALL/ ISLAND
Wall
Island
Wall
Island
CFM/ Lin. Ft
STATIC PRESSURE (" W.G.)
To Calculate Exhaust Duct Length (In)
Example:
Exhaust CFM: 765 and Duct Depth 10" STD
Length = CFM (inches) 104
Length = X inches Duct Depth = X Final Duct Size
Length = 765 CFM (inches) 104
Length = 7.35 inches
Duct Depth = 7.4 then round up to the nearest inch
10" x 8"
Hanging Weight
Ventilator Width 36" 42" 48” 54” 60” Wt. lineal ft. Lbs. 40 45 50 55 60
200 0.25
400 0.25
200 0.25
400 0.25
The above Exhaust Volumes are based upon International Mechanical Code 2006.