Page 93 - 7166 - Rain Garden Handbook
P. 93

C-5







            6.  HOW IS A RAIN GARDEN SIZED TO MEET MINIMUM REQUIREMENT #5?

            Rain Gardens must have a minimum horizontal projected surface area below the overflow (Top Surface of Ponding, shown on page 24 of this
            Handbook) which is at least 5 percent of the area draining to it. The designer may choose a larger size, but Rain Garden performance does not need
            to be predicted with computer models to meet Minimum Requirement #5.

            2012 SWMMWW Reference:
            •  Volume V, Section 5.3 Best Management Practices for On-Site Stormwater Management, BMP T5.14A: Rain Gardens, pages 5-11 through 5-12.