FIRE DAMPERS
Multibladed smoke control damper WKP-P
Classification according to standards: EN13501-4, EN 12101-8 (CE):
» smoke duct, walls and lightweight partition walls:
E600 120 (ved-i↔o) S 1000 C300 AA single, EI 120 (vew-i↔o) S 1000 C10000 AA multi, EI 90 (vew-i↔o) S 1500 C10000 AA multi
Minimum dimensions: 200 x 200 mm Maximum dimensions: 1200 x 800 mm Features:
» electric drivers without return spring
» compact body length 125-230 mm
» tested according to EN 1366-10 up to
1000, 1500 Pa
» air tightness class C according to
EN1751
» maintenance free
SMOKE CONTROL
WKP-P
Mehrlamellen Rauchschutz – Absperrklappe WKP-P
Feuerwiderstandsklasse gem: EN13501-4, EN 12101-8 (CE):
» smoke duct, walls and gypsum plasterboard walls: E600 120 (ved-i↔o) S 1000 C300 AA single, EI 120 (vew-i↔o) S 1000 C10000 AA multi, EI 90 (vew-i↔o) S 1500 C10000 AA multi
Min. Abmessung : 200 x 200 mm Max. Abmessung : 1200 x 800 mm Eigenschaften:
» elektrischer Antrieb mit oder ohne Federrűcklauf
» Länge des Gehäuses : 125 – 230 mm » nach EN 1366-2, bis zum 1000, 1500
Pa geprűft
» Leckluftstrom nach EN 1751-Klasse C » wartungsfrei
ZUP
ZUP Power supply unit for fire safety systems
Power supply for smoke extract fans using frequency converters compliant with EN 12101-10 (CE). The ZUP - series modular power supply unit is designed to supply low and ultra-low voltage (max: 1000V AC, 1500V DC) to smoke and heat control systems, including the power supply of the smoke exhaust and supply air fans controlled by frequency convert- ers. The power supply is also suitable for such devices like fire dampers and smoke control dampers, smoke exhaust windows and skylights, solenoid valves, electromagnetic door holders and gates.
Smoke - Ventilation - Control