Page 76 - Colony Catalog 8th Edition 2
P. 76

PERSONAL PROTECTIVE EQUIPMENT
COLONY
NFPA 70E PPE Requirements
Temp-Test® Arc Protection Clothing
NFPA 70E requires workers to be out tted in Flame Resistant Protective Clothing that meets the requirements of ASTM F1506 when there is a possible exposure to Electrical Arc Flash. The short duration and intense energy presents a unique safety hazard. Our Temp- TestTM Electrical Arc Flash Clothing by Stanco is made exclusively from Westex Indura ultra soft fabric which is 88% cotton and 12% high tenacity nylon for protection, comfort and value. All garments are constructed with Full Raglan sleeves for maximum upper body movement. Front, leg and sleeve enclosures are fastened by Velcro. 5-Thread safety stitch throughout assures minimum seam expo- sure. Trim items, such as Velcro Fasteners, Elastic Take-Ups and Thermo Snap Fasteners are  ame resistant. Please note the following products are 45 Cal/cm2 (ATP Value=45.0). These products are also available in 11 Cal, 35 Cal, 45 Cal, 59 Cal and 100 Cal.
70E PPE Requirements:
Hazard Class 0 (speci c tasks, generally ≤240 V)
Untreated non-melting natural  ber long-sleeve shirt and regular weight (12 oz/yd2) cotton denim jeans
Safety Glasses
Hazard Class 1 (speci c tasks, generally ≤600 V)
Fire-resistive shirt (arc thermal protective value ≥4), AND either regular weight (12 oz/yd2) cotton denim jeans or  re-resistive pants (arc thermal protective value ≥4), OR, coveralls instead of a shirt and pants (arc thermal protective value ≥4)
Hard Hat, Class E Safety Glasses
Hazard Class 2 (speci c tasks, generally ≥600 V)
Untreated non-melting natural  ber long-sleeve shirt AND  re-resistive shirt (arc thermal protective value ≥4), regular weight (12 oz/yd2) cotton denim jeans AND  re-resistive pants (arc thermal protective value ≥4); OR  re-resistive shirt and pants or coveralls (arc thermal protective value ≥8)
Hard Hat, Class E
Safety Glasses or Goggles
Leather Gloves
Leather Work Shoes (not necessarily safety shoes)
Hazard Class 2*, same as Class 2, but add:
Wrap-around face shield covering forehead, ears and neck (arc thermal protective value ≥8), OR double-layer switching hood
Hearing Protection (ear canal inserts)
Hazard Class 3 (speci c tasks, some ≥600 V, generally ≥1 kV)
1. Untreated non-melting natural  ber t-shirt
2. Non-melting long-sleeve shirt and regular weight (12 oz/yd2) cotton denim jeans
3. Fire resistive shirt (arc thermal protective value ≥4) and  re-resistive pants (arc thermal protective value ≥4), OR coveralls (arc thermal protective value ≥4)
4. Coveralls (arc thermal protective value ≥5)
Hard Hat, Class E
Safety Glasses or Goggles
Flash Suit Hood
Leather Gloves
Hearing Protection (ear canal inserts)
Leather Work Shoes (not necessarily safety shoes)
Hazard Class 4 (speci c tasks, generally ≥1 kV)
1. Untreated non-melting natural  ber t-shirt
2. Non-melting long-sleeve shirt and regular weight (12 oz/yd2) cotton denim jeans
3. Fire resistive shirt (arc thermal protective value ≥4) and  re-resistive pants (arc thermal protective value ≥4), OR coveralls (arc thermal protective value ≥4)
4. Flash suit jacket, pants and hood (total arc thermal protective value ≥40)
Hearing Protection (ear canal inserts) Leather Gloves
Safety Glasses/Goggles
Leather Work Shoes
TO ORDER CALL 800-698-0781 OR VISIT COLONYHARDWARE.COM