Page 2 - Highline Display
P. 2
HIGHLINE DISPLAY, Cabinet monitor and status indictor;
LCD Display, CannonGuard interface, includes environmental sensors
1 off Temperature sensor and 1 off Humidity sensor
2 off Power Distribution unit sensor inputs (RS232 and RS485)
Cannon & Other (Geist, APC, Austin Hughes, Servertech)
2 off Electronic lock outputs
1 off Side panel monitoring input
3 off CannonGuard MODBUS ports for daisy chaining of cabinets
1 x LED output for connection to buzzer / indicator or BMS alarm
Managed by Cannon Data Centre Manager
via Master controller / Network interface module.
90-240Vac to 24Vdc Power supply options: ‘-00’ = none, ‘-01’ = one, ‘-02’ = two (resilient)
Mag Mount Master Controller
Master Controller / Network interface module
Magnetic mounting to side panel or roof
Includes Power Supply (90-240Vac)
Has 2 off CannonGuard MODBUS interfaces
one standard 10/100 base T Ethernet connector (100FULL)
SNMP and TCP/IP protocols
Manages 249 CannonGuard modules using one IP address
SNMP traffic to 4 off SNMP trap managers
Allows management of CannonGuard modules from any browser via Cannon Data Centre
Manager Java appet running on a webserver
The Limpit is for remote monitoring and remote changes. You also need it to change
Keypad Code and information on the Highline display.