For the sake of transport is the unit illed with nitrogen. After the whole system installation (indoor
unit CoolTeg, copper piping and outdoor condenser), the unit must be illed with R410A coolant.


standard condenser Conteg AC‑COND1‑35:

















L = 1880 mm; B = 770 mm; H = 730 (‑ 150) mm :: cooling unit CoolTeg XC – AC‑SO‑XC/B4
Suggested values: outdoor temperature 35°C, condensing temperature 45°C



















Use of special condensers:
For higher outdoor temperatures, for quiet applications or in diferent designs with multiple‑circuit exchanger
(one outdoor unit for more indoor units).
Special condensers will be designed to your demands. Enter limit values such as maximum summer tempera‑
ture, CoolTeg unit indoor air temperature, maximum acoustic pressure level in a certain distance, maximum unit
size etc.

Maximal length of refrigerant cupper piping (Ø22mm‑gas/Ø16mm‑liquid) between indoor and outdoor unit
is 30m. Max. diference in height is 5m, if the condenser is located lower than the compressor unit. If the cons‑
denser is located above the indoor unit, the diference shall not exceed 10m. In the case of a diferent building
layouts, the use of indoor and outdoor units must be consulted with Conteg technicians.