SCIENCE & ENGINEERING BUILDING I
CASE STUDY NO. 5
Interior Lighting
The use of energy-efficient light fixtures led to an average installed lighting load of 1.1 watts/gsf, 20% below Title-24 requirements at the time. The lighting design was coordinated for all Phase 1 buildings for both energy efficiency and operations coordination by developing a master fixture schedule. At the time of the Phase 1 projects, the lamp of choice for energy efficiency was the T-5. For lamp dimming purposes, the T5HO lamp was not used.
Heating, Cooling and Ventilation
The heating, cooling and ventilation system for the building was designed following several of the best practices outlined by the Labs21 Program2. These include separate heating and cooling using the room terminal coils to meet room requirements, with pre-cooling of outside ventilation air using an evaporative cooler, and a low-pressure design to minimize fan power requirements.
The system design for each wing of the building is a variable-air-volume (VAV) system, which allows the supply and exhaust airflows to vary based on actual space needs. As in almost all laboratory designs, all of the ventilation air passes through the system only one time. The VAV system therefore will result in a much lower EUI than if a constant amount of air is continuously circulated through the building (a Constant Volume system).
Each wing is served by two equal-sized supply fan units and an exhaust system made up of four exhaust fans. Energy-saving variable frequency drives (VFD’s) on the supply fans provide control of the amount of heating or cooling air being delivered to a room based on a signal from a duct-mounted static pressure sensor. (This is noted here because of a post-occupancy issue pertaining to the pressure sensor location inside the duct.)
There is also no mixing of heated or cooled air streams in the design. Only heating or cooling at the room terminal unit occurs to meet the room requirements. During the summer, the hot dry outside air is pre-cooled using an indirect evaporative cooler at the roof-mounted fan unit, then further cooled at the terminal unit. During the winter, the cold outside air is preheated at the fan unit and further heated at the terminal unit to meet specific room requirements. In the intermedi- ate seasons, there is no pre-heating or pre-cooling; all heating and cooling occurs at the terminal unit.
The system also utilizes a number of methods of low-pressure design for the ductwork and other components to reduce the fan power needed to move the air through the system. Given the large amount of energy expended for this purpose in a laboratory building, this is one of the important features of the mechanical system design.
Finally, the system design includes occupancy sensors in the laboratories, both motion sensors and infrared sensors, to control the electric lighting. These sensors also send a signal to the building management system (BMS) that controls both the temperature of the air at the terminal unit and also the exhaust airflow through the fume hood above the required minimum level for safe operation. When the room is scheduled to be unoccupied, the BMS resets the space tem- perature requirements and the minimum required fume hood exhaust airflow. (This is particularly noted here because of both a post-occupancy issue pertaining to the control system as well as current efforts to improve performance via programming of the “setback” operations.)
All of these design features together effectively lower the EUI for the building and, as required as part of the energy budget, also keep the peak power demand and peak demand on the Chiller Plant below the stated maximums.
2 Labs for the 21st Century, sponsored by the U.S. Environmental Protection Agency and the U.S. Department of Energy, http://www.labs21century.gov/. See also Labs21 Best Practice Guides: http://www.i2sl.org/resources/toolkit/bpg.html
Zero Net Energy Case Study Buildings: Volume 1
(Opposite page) Diagram of low-energy design features (Courtesy of EHDD Architec- ture).