Page 19 - EASA_AR100-2015_0815 APEX_IESCO
P. 19
EASA AR100-2015 Recommended Practice - Rev. August 2015 Section 4, Page 2
insulation systems used in variable frequency drive 4.3.3 Armature Windings
applications should be evaluated to provide adequate An insulation resistance test should be performed.
impedance for the given drive application. [Note: In addition, one or more of the following tests should
There is no industry consensus on a minimum in- be performed:
sulation resistance or impedance value for bearings (1) Growler test.
used with variable frequency drives.] (2) Winding surge test.
(3) Bar-to-bar resistance test.
4.2.8 Phase Balance Test
The phase balance test applies balanced reduced 4.3.4 Shunt, Series, Interpole,
voltage 3-phase power to the stator and the current Compensating and Synchronous
is measured and checked for balance. Rotor Windings
An insulation resistance test should be performed.
4.2.9 Polarity Test In addition, one or more of the following tests should
The polarity test applies direct current, usually to be performed:
a single phase, and the magnetic polarity of the coil (1) Winding resistance test.
groups are checked. (2) Winding surge test.
4.2.10 Dummy Rotor Test (3) AC voltage drop test.
The dummy rotor test uses an artificial rotor such (4) Impedance test.
as a small rotor with a loose fit on a shaft. Reduced 4.3.5 Interconnection of Windings
voltage 3-phase power is supplied to the stator and Shunt, series, interpole, compensating, and syn-
the rotor is moved circumferentially along the bore chronous rotor windings should be tested to ensure
to check for continuous rotor rotation. that the polarities and connections are correct.
4.2.11 Impedance Test Terminal and lead markings should comply with
The impedance test applies an AC voltage to the Subsection 1.6.
two leads of a coil and the voltage and current are 4.4 HIGH-POTENTIAL TESTS
measured. Using Ohm’s Law the impedance is calcu- High-potential tests should be performed on wind-
lated. The impedance of the individual coils is then ings and certain accessories of electrical machines
compared for relative equality among coils that are at a specified voltage. To avoid excessive stressing
intended to have equal electromagnetic qualities. of the insulation, repeated application of the high-
potential test voltage is not recommended.
4.3 RECOMMENDED WINDING TESTS Machines to be tested must be clean and dry.
Windings should be tested to ensure that there Inspection and insulation resistance tests with
are no grounds (earth faults), short circuits, open acceptable results should be performed before the
circuits, incorrect connections or high resistance high-potential tests. Insulation resistance tests
connections. should be repeated at the completion of the high-
4.3.1 Stator and Wound-Rotor Windings potential tests.
The IR, winding surge and winding resistance When a high-potential test is conducted on an as-
tests should be performed. In addition one or more sembled brushless exciter and synchronous machine
of the following tests may be performed: field winding, the brushless circuit components (di-
(1) Phase-balance test. odes, thyristors, etc.) should be short-circuited (not
(2) Polarity test. grounded/earthed) during the test.
(3) Artificial rotor (dummy rotor) test (low voltage High-potential tests should be successively ap-
energization). plied between each winding or electric circuit under
(4) Polarization index test or dielectric absorption test and the grounded (earthed) frame (or core) of
the machine. All other windings or electric circuits
test.
(5) Insulation dissipation or power factor test. not under test should be connected to the grounded
(earthed) frame (or core).
(6) Turn-to-turn test. Capacitors of capacitor-type motors must be left
(7) Partial discharge testing for inception and connected to the winding in the normal manner for
extinction voltage levels. machine operation (running or starting).
4.3.2 Squirrel Cage Windings Electrical machines may be tested using AC or DC
One or both of these tests should be performed: high-potential test equipment. The DC test voltage
(1) Growler test. should be 1.7 times the specified AC voltage. A fail-
(2) Single-phase test. ure under test can be less damaging to the winding
15