Page 38 - Panduan Simulasi Homer KKP PLTS Hybrid
P. 38
Input Library Gas Engine
Library data assumptions :
Components Unit Value
Netto Capacity MW 3
Capacity Factor (%) 60%
Annual kWh Sales MWh/year 15768
Net Plant Heat Rate BTU/kWh 8497
USD/MMBTU 8.6
Fuel Price USD/scf 0.0086
USD/m^3 0.304
Heat Gas Value BTU/scf 1000
BTU/h 25,491,000
Gas Consumptions scf/h 25,491
m^3/h 722
Output Heat Rate Gas Consumptions
% Load kW BTU/kWh scf/h m^3/h
30% 900 10152 9137 259
40% 1200 9525 11430 324
50% 1500 9230 13845 392
60% 1800 9005 16210 459
70% 2100 8841 18566 526
80% 2400 8718 20922 592
90% 2700 8574 23150 656
100% 3000 8497 25491 722