Performance data notes





       Speed / torque & speed / current curves                                                               11






                  DOL starting
                  Typical speed/current curve                   Typical speed/torque curve
















                  (I )    Starting current                     During the run up period in Star, there must be an
                   A
                  (I )    Full load current                    adequate excess of motor torque over the load
                   N
                  (M )    Starting torque or locked rotor torque  torque. The change to Delta must not occur until
                    A
                  (M )    Pull up torque or run up torque      the motor is near the operating speed. Refer to
                    S
                  (M )    Pull out torque or breakdown torque  Brook Crompton for running up against a load in
                    K
                  (M )    Full load torque                     excess of 70% full load during Star Delta starting.
                    N
                  Torque/speed curves for specific motors can be  Performance figures are subject to IEC
                  supplied on request.                         tolerances. Performance figures are based on a
                                                               400 volt winding.
                                                                      2
                                                                  2
                                                               J (WK or WR ) =  GD 2
                                                                            4
                                                                       kgm 2
                                                               J in lb ft =
                                                                   2
                                                                       0.042
           Connection diagrams





                    Star Delta                     Dual voltage                  Thermistors




                         W2  U2  V2                      W2  U2  V2
                                    D.O.L
                                                                    ∆
                                      ∆
                          U1  V1  W1                     U1  V1  W1
                           L1  L2  L3                     L1  L2  L3
                           W2  U2  V2                     W2  U2  V2              P1             P2
                                    Y∆                              Y
                           U1  V1  W1                     U1  V1  W1


                          Motors => 4kW                                          Connect to thermistor control unit.
   6   7   8   9   10   11   12   13   14   15   16