Page 3 - Appendix A - Fire Alarm System
P. 3
Fire Alarm System
An open protocol, conventional fire alarm system with adequate zones is to be
installed to meet the design requirements of BS5839-1: 2017 Type L3.
Design elements of this system should satisfy the requirements of the Equality Act
2010.
Type L3 requires automatic optical smoke detectors to be fitted in all escape routes
and any room >1m which open onto escape routes. (Staff toilets and cold stores are
2
an exception to this requirement)
Automatic optical smoke detectors with remote indicators are to be installed and
located in any ceiling void >800mm in height.
Manual call points must be located at each exit to fresh air, storey exits from 1 zone
to another, at the point where upper or lower floors discharge to a staircase and be
positioned 1.2m (To centre) from finished floor level, and fitted complete with
protective covers.
Flashing beacons shall be used throughout, to provide a visual warning in alarm
conditions for those with hearing impairments. Particularly in areas where members
of the public may be in attendance and also disabled toilets.
The fire alarm sounders should be consistent throughout i.e. all bells or all electronic
sounders and achieve a volume of 65dB or 5dB above ambient background noise.
The entire system must be wired in 60 minute fire rated cable secured with metal
clips or supported on suitable cable trays.
The system must be supported with battery back-up which will be capable of running
the system for 24 hours following full power failure and be suitable of ringing the
sounders for a minimum period of 30 minutes.
The system must be remotely monitored for activation particularly if there is adjoining
accommodation above or adjacent to the building.
All organisations who design, install, test or commission this system must be a BAFE
registered organisation and certified to SP203-1.
Document Classification Final Document Ref: 3.1-RCS-RHSE-(800)-265 Version 1.1