H13 Structural glass assemblies

DESIGN REQUIREMENTS

211 DESIGN
      • Structural glass assembly: Complete the design.
      • Related works: Coordinate in the design.

341 WEATHER RESISTANCE
      • Air leakage through sealant joints: None.
      • Water leakage through the structural glass assembly and perimeter junctions:
          None.

391 THERMAL STRESS IN GLAZING SAFETY
      • Glass panes and units: Must have adequate resistance to thermal stress generated
          by orientation, shading, solar control and construction.

411 ACCURACY OF ERECTION
      • Permitted deviation in glass joint width (maximum): ±3 mm.

421 SECURITY
      • Threaded assembly fixings and assembly support fixings: Locked or pinned at
          completion of structural glazing to prevent rotation due to building movement and
          unauthorized adjustment.

475 DAYLIGHT PERFORMANCE
      • Daylight calculations: In accordance with BS 8206-2, CIBSE 'Lighting guide LG10'
          and BRE 'Site layout guide'.
      • BREEAM requirements:
          - Submit the following: Daylight performance schedule and Design plans for each
             floor in the building with each room/ area labelled for use.
          - Calculations showing: Average daylight factor expressed as a percentage for
             each room/ area.

480 VIEW OUT
      • Glazed areas/ opening sizes and position: Designed to meet BREEAM 'View out'
          criteria for relevant building type.
      • Submit design plan and elevation drawings showing the following:
          - All BREEAM defined 'relevant areas' dependant on building type and room
             depths.
          - Actual or notional workstation/ desk layouts.
          - Glazed/ open areas.
      • Submit site plan showing: Building location and proximity to external obstructions.

485 POTENTIAL FOR NATURAL VENTILATION
      • Submit design plan and elevation drawings, and calculations confirming the
          following:
          - Locations of openings;
          - Types of glazed areas/ ventilators and total openable areas; and
          - Types and degree of user-controls.