Page 311 - 3M ELECTRICAL PRODUCTS CATALOG - 596-PAGES
P. 311

IronwoodPremium_474115_Catalog-On-Demand7.QXD  6/16/2015  11:59 PM  Page 312










                   Three Core Tape Shield, Wire Shield & UniShield® Cable, 5-35 kV: 3M™ Cold Shrink QT-III Terminations: Outdoor Skirted
                   Kits


                   3M™ Cold Shrink QT-III Inverted Termination Kit 7600-S-INV-3RJS Series for 5-
                   25/28 kV

                   3M™ Cold Shrink QT-III Inverted Termination Kit 7600-S-INV-3RJS Series are designed to accommodate medium voltage 3/C shielded power cable kits for
                   7600-3-RJS Series cabinet-mount installations and can be used on cables with or without ground wires. Each termination kit is supplied with all the
                   materials required for terminating one three-conductor cable. Terminal and/or lug must be ordered separately.
                   *For Wire or UniShield® shielding, please contact 3M for technical assistance.

                        Number of Conductors  Three Conductor
                                          Tape Shield (Armored or Unarmored),
                             Shielding Type
                                          Wire Shield*, UniShield®*
                             Indoor/Outdoor  Outdoor
                             Breakout Boot  No
                        Insulation Rejacketing  Yes
                                 No. Skirts  4
                                          3.3 kV, 5 kV, 6.6 kV, 8 kV, 10 kV, 15 kV,
                                  Voltage
                                          20 kV, 25/28 kV
                                          1 kit per case (one three-phase termi-
                                Packaging
                                          nation per kit)
                                                         7693-S-4-INV-3-RJS                     7695-S-4-INV-3-RJS
                   UPC                                     054007-04720                           054007-04721
                   BIL                                       200 kV                                  200
                   Max. Installed Length                   16.0” (406 mm)                         16.0” (406 mm)
                   Insulation O.D. Range               0.92”-1.18” (23,4-30,0 mm)             1.18-1.52” (30,0-38,6 mm)
                   Conductor Size 3.3 kV IEC (JIS)    240-300 mm² (200-250 mm²)                  - (300-325 mm²)
                   Conductor Size 5.0 kV AEIC              500-750 kcmil                          800-1000 kcmil
                   Conductor Size 6.6 kV IEC (JIS)    185-300 mm² (150-250 mm²)                  - (300-325 mm²)
                   Conductor Size 8 kV AEIC                400-600 kcmil                          750-1000 kcmil
                                                                                                      -
                                                           185-300 mm²
                   Conductor Size 10 kV IEC           120-185 mm² (250-450 kcmil)            200-325 mm² (500-750 kcmil)
                   Conductor Size 15 kV IEC (AEIC)
             5-46 kV Medium Voltage Terminations,  Conductor Size 20 kV IEC  2/0 AWG-250 kcmil    240-300 mm²
                                                           95-185 mm²
                                                                                                  300-500 kcmil
                   Conductor Size 25/28 kV AEIC


























           312                                                 FAX: 800-245-0329
   306   307   308   309   310   311   312   313   314   315   316