THE TEST.
SYSTEM. (N1103.1).
OF THE FOLLOWING:
FROM DETERIORATION.
CLOTHES DRYER EXHAUST DUCTS:
VENTILATION SYSTEM IS NOT OPERATING. (N1103.5).
2. INDICATES EXISTING CEILING MOUNTED RETURN AIR
INDICATES LOCATIONS OF NEW AIR SUPPLY REGISTERS.
DUCT, UP THROUGH THE ROOF WITH FLASHING AND CAP.
DUCTS IN FLOOR TRUSSES SHALL BE INSULATED TO MINIMUM R-6.
PENETRATIONS OF THE BUILDING THERMAL ENVELOPE. (N1102.4.1.2).
MECHANICAL NOTES
SUPPLY AND RETURN DUCTS SHALL BE INSULATED TO A MINIMUM R-8.
OR EQUAL TO 3 CFM PER 100 SQUARE FEET OF CONDITIONED FLOOR AREA.
TOTAL LENGTH IS LIMITED TO A 14'-0" MAXIMUM COMBINED HORIZONTAL AND
SUPPORT AT REGISTERS. DIFFUSERS AND GRILLES SHALL BE MECHANICALLY
ARE PVC AND EXPOSED TO DAYLIGHT SHALL BE PAINTED TO PROTECT THE PIPE
AND SHALL TERMINATE IN A APPROVED LOCATION SUCH AS TO THE EXTERIOR
OF THE BUILDING OR TO A LAVATORY TAILPIECE. ANY CONDENSATE DRAINS THAT
FASTENED TO RIGID SUPPORTS OR STRUCTURAL MEMBERS ON AT LEAST TWO
MECHANICAL EQUIPMENT SHALL HAVE 3/4" PRIMARY CONDENSATE DRAIN LINES
OFFICIAL. TESTING SHALL BE PERFORMED AT ANY TIME AFTER CREATION OF ALL
VERTICAL LENGTH AND FOR EACH 90 DEGREE ELBOW IN EXCESS OF TWO, THAT
TWO FEET (2') BE DEDUCTED FROM THE 14' FEET. PROVIDE BACKDRAFT DAMPER
PER MECHANICAL CONTRACTOR.) PROVIDE CONDENSATION LINES AS REQUIRED.
INTERIOR AIR HANDLERS AND EXTERIOR COMPRESSORS AS SHOWN. (VERIFY SIZES
OPPOSITE SIDES IN ADDITION TO BEING CONNECTED TO THE DUCT WORK THEY SERVE.
BLOWER DOOR AT A PRESSURE OF 0.2 INCHES W.G. (50 PASCALS). TESTING SHALL BE
PROVIDE KITCHEN EXHAUST FAN MINIMUM 100 CFM AT HOOD, CONNECTED TO METAL
ALL REGISTERS SHALL BE TAPED OR OTHERWISE SEALED DURING THE TEST. IF THE AIR
AND EXHAUSTS SHALL HAVE AUTOMATIC OR GRAVITY DAMPERS THAT CLOSE WHEN THE
DUCTS, AIR HANDLERS, AND FILTER BOXES SHALL BE SEALED. JOINTS AND SEAMS SHALL
ROUGH-IN TEST: TOTAL LEAKAGE SHALL BE LESS THAN OR EQUAL TO 4 CFM PER 100 FT2 OF
CONDUCTED BY AN APPROVED THIRD PARTY. A WRITTEN REPORT OF THE RESULTS OF THE
THE BUILDING SHALL BE PROVIDED WITH VENTILATION THAT MEETS THE REQUIREMENTS OF
(25 PA) ACROSS THE SYSTEM, INCLUDING THE MANUFACTURER'S AIR HANDLER ENCLOSURE.
SECTION M1507 OR WITH OTHER APPROVED MEANS OF VENTILATION. OUTDOOR AIR INTAKES
0.1 INCHES W.G. (25 PA) ACROSS THE ENTIRE SYSTEM, INCLUDING THE MANUFACTURER'S AIR
HANDLER IS NOT INSTALLED AT THE TIME OF THE TEST, TOTAL LEAKAGE SHALL BE LESS THAN
CONDITIONED FLOOR AREA WHEN TESTED AT A PRESSURE DIFFERENTIAL OF 0.1 INCHES W.G.
RATE OF NOT EXCEEDING 5 AIR CHANGES PER HOUR. TESTING SHALL BE CONDUCTED WITH A
COMPLY WITH SECTION M1601.4.1, (N1103.2.2). DUCT TIGHTNESS SHALL BE VERIFIED BY EITHER
SQUARE FEET OF CONDITIONED FLOOR AREA WHEN TESTED AT A PRESSURE DIFFERENTIAL OF
THE BUILDING OR DWELLING UNIT SHALL BE TESTED AND VERIFIED AS HAVING AN AIR LEAKAGE
AT LEAST ONE THERMOSTAT SHALL BE PROVIDED FOR EACH SEPARATE HEATING AND COOLING
HANDLER ENCLOSURE. ALL REGISTER BOOTS SHALL BE TAPED OR OTHERWISE SEALED DURING
TEST SHALL BE SIGNED BY THE PARTY CONDUCTING THE TEST AND PROVIDED TO THE BUILDING
POST-CONSTRUCTION TEST: TOTAL LEAKAGE SHALL BE LESS THAN OR EQUAL TO 4 CFM PER 100