Page 38 - ESP Participant Guide_Neat
P. 38

Module 4: NGV Safety Practices and Procedures

             If Your Facility Has a
             Methane Gas
             Detection System






















                                  When present, the methane gas detection system detects methane at potentially unsafe
                                  levels inside a maintenance facility.  The methane gas detection system:
                                  ▪  Activates at 25% LFL and may perform some or all the following:
                                         o  Activates an exterior red light
                                         o  Activates internal audible/visual alarms
                                         o  Activates emergency exhaust fans
                                         o  Activates and opens make-up air (roll-up doors, etc.)
                                         o  Deactivates heating system
                                         o  Deactivates welding receptacles
                                         o  Notifies your organization’s security department
                                         o  Notifies fire department, if required

































                                           NGV Essentials and Safety Practices                                  © 2019 NGVi All Rights Reserved   Page 4-3