Page 71 - ESP Participant Guide_Neat
P. 71

Module 8: LNG Vehicle Systems and Safety Practices


           Lesson 8.4: LNG Vehicle Safety Practices

             General Safety       ▪  Do not allow an LNG vehicle into a facility that has not been modified specifically
             Practices               for LNG and/or that does not have a working methane detection system
                                  ▪  Wear Personal Protective Equipment (PPE) as prescribed by manufacturer

             Welding/Hot Work     ▪  Always use welding blanket to protect LNG fuel system components when welding
                                     on or around LNG vehicles
                                  ▪  Your company may require additional procedures, such as a fire watch













             If You Detect an     ▪  LNG is unodorized and cannot be detected by humans
             LNG Leak             ▪  NEVER bring a leaking LNG vehicle into the maintenance facility - Leave the vehicle
                                     outdoors
                                  ▪  Identify the source of the leak
                                  ▪  Repair according to manufacturer’s procedures

             Methane Gas          While optional for CNG maintenance facilities,
             Detection Systems    methane gas detection systems are REQUIRED
                                  by code for all LNG maintenance facilities

                                  When present, the methane gas detection
                                  system detects methane at potentially unsafe
                                  levels inside a maintenance facility.  The
                                  methane gas detection system:

                                  ▪  Activates at 25% LFL and may perform
                                     some or all the following:
                                         o  Activates an exterior red light
                                         o  Activates internal audible/visual
                                             alarms
                                         o  Activates emergency exhaust fans
                                         o  Activates and opens make-up air (roll-up doors, etc.)
                                         o  Deactivates heating system
                                         o  Deactivates welding receptacles
                                         o  Notifies your organization’s security department
                                         o  Notifies fire department, if required


                                           NGV Essentials and Safety Practices                                  © 2019 NGVi All Rights Reserved   Page 8-10