Slide Topic                      Content                Notes
Natural Gas Leak Detection
                                Hand-held electronic gas
                                   detector

                                Leak detection solution

If You Detect a Leak            Leave the vehicle outdoors
                                Shut off the cylinder valves
Prior to Bringing CNG Vehicle   Identify location of leak
into Maintenance Facility       Depressurize that portion of

                                   the system
                                Repair the leak according to

                                   manufacturer’s procedures

                                Use rundown procedure to
                                   depressurize fuel system

Rundown Procedure              1. Confirm the ¼ turn manual
                                   shutoff valve is open.

                               2. Shut off all cylinder valves or
                                   disconnect electric solenoid
                                   valves.

                               3. Start the engine.
                               4. Run until it stalls and will not

                                   restart.
                               5. When engine will not run,

                                   the high-pressure fuel system
                                   should have low pressure.
                               6. Check pressure gauges to
                                   confirm
                               7. Open bleed valve on the
                                   high-pressure side and the
                                   petcock on the low-pressure
                                   coalescing filter.
                                    If there is no bleed valve,

                                        carefully loosen the drain
                                        on the bottom of the
                                        high pressure filter (if
                                        present).
                                    If there is no drain plug,
                                        contact your supervisor
                                        or the manufacturer.