Page 36 - AFVi CNG & LNG Participant Guide
P. 36

Module 4: NGV Safety Practices and Procedures

             Safety Practices for     Use welding blanket to protect CNG fuel system components
             Welding and Hot
             Work

             If Your Facility Has a
             Methane Gas
             Detection System






















                                  When present, the methane gas detection system detects methane at potentially unsafe
                                  levels inside a maintenance facility.  The methane gas detection system:
                                    Activates at 25% LFL and may perform some or all the following:
                                      o  Activates an exterior red light
                                      o  Activates internal audible/visual alarms
                                      o  Activates emergency exhaust fans
                                      o  Activates and opens make-up air (roll-up doors, etc.)
                                      o  Deactivates heating system
                                      o  Deactivates welding receptacles
                                      o  Notifies your organization’s security department
                                      o  Notifies fire department, if required


























                                           NGV Essentials and Safety Practices (CNG & LNG)                            © 2024 AFVi All Rights Reserved    Page 4-3