Page 371 - VillageOrdinanceBook
P. 371
Chapter 14 – Building Code
Nonflammable. Not flammable.
Multifamily Dwelling” means an apartment building, rowhouse, town house, house,
condominium or manufactured building, as defined in Wis. Stat. §101.71(6), that
does not exceed sixty (60) feet in height or six (6) stories and that consists of three
(3) or more attached dwelling units the initial construction of which is begun on or
after January 1, 1993. "Multifamily dwelling" does not including a facility licensed
under Chapter 50 of the Wisconsin Statutes.
Story. That part of a building comprised between a floor and the floor or roof next
above.
(2) INSTALLATION REQUIRED. Every building or structure hereafter constructed in
the Village shall have an approved automatic sprinkler system installed and
maintained when occupied in whole or in part for the following purposes:
(a) Buildings for the manufacture, storage or sale of combustible goods or
merchandise.
1. Fire-resistive buildings. Throughout every fire-resistive building
occupied in whole for the manufacture, storage or sale of combustible
goods or merchandise if any of the following apply:
a. Over 10,000 sq. ft. in area.
b. Over one story in height and exceeding 6,000 sq. ft. in area.
c. Over 4 stories in height, regardless of area.
2. Nonfire resistive buildings. Throughout every nonfire resistive building
occupied, in whole or in part, for the manufacture, storage or sale of
combustible goods or merchandise if any of the following apply:
a. Over 7,000 sq. ft. in area.
b. Over one story in height, and exceeding 4,000 sq. ft. in area.
c. Over 3 stories in height, regardless of area.
(b) Garages. Throughout the following garages if any of the following apply:
39