Page 85 - Updated SuDS Design & Evaluation Guide-Newham V3 Spreads
P. 85

Detailed Design  9.5.4  Calculation inputs  9.5.4.3  Making allowances for interception losses                    Detailed Design

      As a rule of thumb, where the total wetted
 9.5.4.1  Rainfall data selection
      area of SuDS components equates to at least
 Rainfall depths and intensities for a range of
      25% of the development area (all buildings
 return periods and storm durations is one of
      and hard surfaces) then it is acceptable to
 the key calculation inputs.
      make an allowance for interception losses.
                                                              For more detailed analysis methods
 The choice of rainfall data can have a
      This loss can be applied within storage
 significant effect on the volume of storage
 calculated.
      by 5mm.
 FEH 2013 rainfall data is considered the most   calculations by reducing the rainfall depths   see SuDS Manual Section 24.8
 up-to-date data availabale and therefore
 recommended for use.   9.5.4.4  Defining infiltration rates
 FEH 2013 rainfall data can be sourced
 Where FSR rainfall values are used the   The specified infiltration test methodology   For example, tests should not be undertaken
 designer must demonstrate that rainfall   online at fehweb.ceh.ac.uk  should be representative of the proposed   1.5m below ground level when shallow
 values are consistent with FEH 2013 data.  design.          infiltration is proposed from permeable
                                                             pavement, rain gardens or basins which will
      The depth of water and depth of test trench
                                                             be located close to ground surface.
      below ground level should seek to replicate
      the attributes of the proposed infiltration
 9.5.4.2  Defining runoff coefficients (Cv)  system.


 79   In extreme rainfall conditions the losses   Some modelling software packages contain   Bromsgrove Civic Centre re-development.  80
 anticipated from hard development surfaces   ‘Default’ Cv values (0.75 Summer, 0.84   Permeable block and slab paving with a central grass detention basin
 such as roofs or paved areas are anticipated   Winter) which assume that there will be 25%   provide a fully integrated infiltrating SuDS scheme.
 to be minimal.   summer and 16% winter losses from hard
 surfaces.
 The designer must evaluate the runoff
 coefficient (Cv) for the types of surfaces   These default values should not be used for
 contributing runoff to the storage location.   storage estimation calculations.
 Sewers for adoption (Section C5.1)
 The designer must justify where a Cv of less
 recommends assuming 100% runoff from
 than 0.9 is used for calculations.
 impermeable areas which equates to a Cv of
 1.0.   Where a reasonable amount of permeable
 surface contribution to SuDS storage, then
 Runoff coefficients of 0.95 for roofs and 0.9
 this should be considered within calculations.
 for paved areas would be considered
 The ‘UKSuDS’  website was recently updated
 acceptable by the LLFA where drainage is
 to allow input for permeable surface runoff
 not being adopted by a Water and Sewerage
 contribution within attenuation calculations.
 Company (Thames Water).






 Newham Council SuDS D & E Guide                                                                        © 2020 McCloy Consulting & Robert Bray Associates  Newham Council SuDS D & E Guide                                                                        © 2020 McCloy Consulting & Robert Bray Associates
   80   81   82   83   84   85   86   87   88   89   90