P. 164

FIRE PROTECTION AND LIFE SAFETY SYSTEMS



                    support visible alarm notification appliances in   907.6.4.2 High-rise buildings. In high-rise buildings, a
                    accordance with Chapter 11 of ICC A117.1. Such     separate zone by floor shall be provided for each of the
                    capability shall accommodate wired or wireless     following types of alarm-initiating devices where pro-
                    equipment. The future capability shall include one  vided:
                    of the following:                                    1. Smoke detectors.
                       1. The interconnection of the building fire alarm  2. Sprinkler waterflow devices.
                         system with the unit smoke alarms.
                                                                         3. Manual fire alarm boxes.
                       2. The replacement of audible appliances  with
                         combination audible/visible appliances.         4. Other approved types of automatic fire detection-
                                                                            devices or suppression systems.
                       3. The future extension of the existing wiring
                         from  the unit smoke alarm locations to     907.6.5 Access.  Access shall  be provided to  each fire
                         required locations for visible appliances.  alarm device and notification  appliance for periodic
                                                                     inspection, maintenance and testing.
             907.6 Installation and  monitoring.  A fire alarm  system
             shall be installed and monitored in accordance with Sections  907.6.6 Monitoring. Fire alarm systems required by this
             907.6.1 through 907.6.6.2 and NFPA 72.                  chapter or by the  International Building Code  shall be
                                                                     monitored by an  approved supervising station in accor-
               907.6.1 Wiring.  Wiring  shall comply with the require-  dance with NFPA 72.
               ments of NFPA 70 and NFPA 72. Wireless protection sys-
               tems utilizing radio-frequency  transmitting devices  shall  Exception: Monitoring by a supervising station is not
               comply  with the special requirements for  supervision of  required for:
               low-power wireless systems in NFPA 72.                    1. Single-  and multiple-station smoke alarms
                                                                            required by Section 907.2.10.
               907.6.2 Power supply. The primary and secondary power
               supply for the fire alarm system shall be provided in     2. Smoke detectors in Group I-3 occupancies.
               accordance with NFPA 72.                                  3. Automatic sprinkler  systems in  one- and  two-
                  Exception: Backup power for single-station and multi-     family dwellings.
                  ple-station smoke alarms as required  in Section     907.6.6.1 Automatic telephone-dialing devices. Auto-
                  907.2.10.6.                                          matic telephone-dialing devices used to transmit an
               907.6.3  Initiating device identification. The fire alarm  emergency alarm shall not be connected to any  fire
               system shall identify the specific initiating device address,  department telephone number unless approved by the
               location, device type, floor level where applicable and sta-  fire chief.
               tus including  indication of normal,  alarm,  trouble and  907.6.6.2 Termination of monitoring service.  Termi-
               supervisory status, as appropriate.                     nation of fire alarm monitoring services shall be in
                  Exceptions:                                          accordance with Section 901.9.
                    1. Fire alarm systems in single-story buildings less  907.7 Acceptance tests and completion. Upon completion
                                                2
                       than 22,500 square feet (2090 m ) in area.  of the installation, the fire alarm system and all fire alarm
                                                                  components shall be tested in accordance with NFPA 72.
                    2. Fire alarm systems that only include manual fire
                       alarm boxes, waterflow initiating devices and not  907.7.1 Single- and multiple-station alarm devices.
                       more than 10 additional alarm-initiating devices.  When the installation of the alarm devices is complete,
                                                                     each device and interconnecting wiring for multiple-sta-
                    3. Special initiating devices that do not support indi-
                       vidual device identification.                 tion alarm devices shall be tested in accordance with the
                                                                     smoke alarm provisions of NFPA 72.
                    4. Fire alarm systems or devices that are replacing
                       existing equipment.                           907.7.2 Record of completion. A record of completion in
                                                                     accordance with NFPA 72 verifying that the system has
                  907.6.3.1 Annunciation. The initiating device status  been installed and tested in accordance with the approved
                  shall be annunciated at an approved on-site location.  plans and specifications shall be provided.
               907.6.4 Zones. Each floor shall be zoned separately and a  907.7.3 Instructions. Operating, testing and maintenance
                                                         2
               zone shall not exceed 22,500 square feet (2090 m ). The  instructions and record drawings (“as builts”) and equip-
               length of any zone shall not exceed 300 feet (91 440 mm)  ment specifications shall be provided at an approved loca-
               in any direction.                                     tion.
                  Exception: Automatic sprinkler system zones shall not  907.8 Inspection,  testing and maintenance.  The mainte-
                  exceed the area permitted by NFPA 13.           nance and testing schedules and procedures for fire alarm and
                  907.6.4.1 Zoning indicator panel. A zoning indicator  fire detection systems shall be in accordance with Sections
                  panel and the associated controls shall be provided in  907.8.1 through 907.8.5 and NFPA 72. Records of inspec-
                  an approved location. The visual zone indication shall  tion, testing and maintenance shall be maintained.
                  lock in until the system is reset and shall not be can-  907.8.1 Maintenance required. Where required for com-
                  celed by the operation  of  an audible  alarm-silencing  pliance with the provisions of this code, devices, equip-
                  switch.                                            ment, systems, conditions, arrangements, levels of