Page 255 - 2018_IFC
P. 255

ENERGY SYSTEMS



         with NFPA 2 and NFPA 70, the manufacturer’s installation  system  is  installed, unless otherwise  approved by the  fire
         instructions and the listing.                        code official.
         1205.5 Residential  use. Stationary fuel cell power systems  1205.11 Ventilation and exhaust. Ventilation and exhaust
         shall  not be installed in  Group R-3 and R-4  buildings, or  for stationary fuel cell power  systems shall be provided in
         dwelling units  associated  with Group R-2  buildings unless  accordance with NFPA 853.
         they are specifically listed for residential use.    1205.12 Fire  suppression. Fire suppression for  stationary
         1205.6 Indoor installations. Stationary fuel cell power sys-  fuel cell power  system installations shall be provided in
         tems installed in indoor locations shall comply with Sections  accordance with NFPA 853.
         1205.6 through 1205.6.2. For purposes of this section, an  1205.13 Gas detection systems. Stationary fuel cell power
         indoor location  includes a roof and 50 percent  or greater  systems shall be provided with a gas detection system. Detec-
         enclosing walls.                                     tion shall be provided in approved locations in the fuel cell
           1205.6.1 Listed.  Stationary fuel cell  power systems  power system enclosure, the exhaust system or the room that
           installed indoors shall be specifically listed and labeled for  encloses the fuel cell  power system. The system shall be
           indoor use.                                        designed to activate at a flammable gas concentration of not
                                                              more than 25 percent of the lower flammable limit (LFL).
           1205.6.2 Separation. Rooms containing  stationary fuel
           cell power systems shall be separated from the following  1205.13.1 System activation.  The  activation of the gas
           occupancies by fire barriers or horizontal assemblies, or  detection system shall automatically:
           both, constructed in accordance  with  the  International  1. Close  valves between the gas  supply and  the fuel
           Building Code.                                            cell power system.
              1. Group B, F, M, S and U occupancies by 1-hour fire-  2. Shut down the fuel cell power system.
                resistance-rated construction.
                                                                   3. Initiate local audible and visible alarms in approved
              2. Group A, E, I and  R occupancies by 2-hour fire-    locations.
                resistance-rated construction.
              Exception: Stationary fuel cell power systems with an
              aggregate rating less than 50 kW shall not be required            SECTION 1206
              to be separated from other occupancies provided that  ELECTRICAL ENERGY STORAGE SYSTEMS
              the systems comply with Section 9.3 of NFPA 853.  1206.1 Scope. The provisions in this section are applicable to
         1205.7  Vehicle impact protection. Where  stationary fuel  energy storage systems designed to provide electrical power
         cell power systems are subject to impact by a motor vehicle,  to a building or facility. These systems are used to provide
         vehicle impact protection shall be provided in accordance  standby or emergency power, an uninterruptable power sup-
         with Section 312.                                    ply, load shedding, load sharing or similar capabilities.  **
         1205.8 Outdoor installation. Stationary fuel cell power sys-  1206.2 Stationary storage battery systems. Stationary stor-
         tems located outdoors shall be separated by not less than 5  age battery systems having capacities  exceeding the values
         feet (1524 mm) from the following:                   shown in Table 1206.2 shall comply with Section 1206.2.1
           1. Lot lines.                                      through 1206.2.12.6, as applicable.
                                                                 1206.2.1 Permits. Permits shall be obtained for the instal-
           2. Public ways.
                                                                 lation and operation of stationary storage battery systems
           3. Buildings.
                                                                 in accordance with Section 105.7.2.
           4. Stored combustible materials.
                                                                 1206.2.2 Construction documents. The following infor-
           5. Hazardous materials.                               mation shall be provided with the permit application:
           6. High-piled stock.                                    1. Location and layout diagram of the room in which
           7. Any portion of a designated means of egress system.    the stationary storage battery system is to be
                                                                     installed.
           8. Other exposure hazards.
                                                                   2. Details on hourly fire-resistance-rated  assemblies
         1205.9 Fuel supply. The design, location and installation of
         the fuel supply for stationary fuel cell power systems shall  provided.
         comply with  Chapter  53, Chapter  58 and the  International  3. Quantities and types of storage batteries and battery
         Fuel Gas Code, based on the particular fuel being supplied to  systems.
         the system.                                               4. Manufacturer’s specifications, ratings and listings of
         1205.10 Manual shutoff. Access to a manual shutoff valve    storage batteries and battery systems.
         shall be provided for the fuel piping within 6 feet (1829 mm)  5. Details on energy management systems.
         of any fuel storage tank serving the fuel cell and within 6 feet  6. Location and content of signage.
         (1829 mm) of the power system. If the fuel tank and the sta-
         tionary fuel cell  power system are less than  12 feet (3658  7. Details on fire-extinguishing, smoke detection and
         mm) apart, a single shutoff valve shall be permitted. If the  ventilation systems.
         stationary fuel cell power system is located indoors, the shut-  8. Rack storage  arrangement, including  seismic sup-
         off valve shall be located outside of the room in which the  port criteria.

         222                                                                        2018 INTERNATIONAL FIRE CODE ®