Page 298 - 2018_IFC
P. 298

FLAMMABLE FINISHES



                  quantity of solvent used in a machine shall not exceed  2404 when approved and where utilizing Class IIIA
                  the design capacity of the machine.                    or IIIB combustible liquids.
                  2403.3.5.2 Within spray booths and  spray rooms.     2. In buildings other than Group A, E, I or R occupan-
                  Where solvents are used for cleaning spray nozzles and  cies, approved limited spraying space in accordance
                  auxiliary equipment  within spray booths and  spray    with Section 2404.9.
                  rooms, the  ventilating equipment shall be operated  3. Resin application areas  used for manufacturing of
                  during cleaning.
                                                                         reinforced plastics complying with Section  2409
               2403.3.6 Class II and III liquids. Solvents used outside  shall not be required to be located in a spray room,
               of spray booths, spray rooms or listed and approved spray  spray booth or spraying space.
               gun and equipment cleaning machines shall be restricted
               to Class II and III liquids.                       2404.3 Design and construction. Design and construction of
                                                                  spray rooms, spray booths and spray spaces shall be in accor-
             2403.4 Operations and maintenance.  Flammable vapor  dance with Sections 2404.3.1 through 2404.3.3.1.
             areas, exhaust fan blades and exhaust ducts shall be kept free
             from the accumulation of deposits of combustible residues.  2404.3.1 Spray rooms. Spray rooms shall be constructed
             Where excessive residue accumulates in such areas, spraying  and designed in accordance with Section 416 of the Inter-
             operations shall be  discontinued  until conditions  are cor-  national Building Code and Section 2404.3.2 of this code,
             rected.                                                 and shall comply with Sections 2404.4 through 2404.8 of
                                                                     this code.
               2403.4.1 Tools. Scrapers, spuds and other tools used for
               cleaning purposes shall be constructed of nonsparking  2404.3.2 Floor. Combustible floor construction in spray
               materials.                                            rooms shall be covered  by  approved, noncombustible,
                                                                     nonsparking material,  except  where combustible cover-
               2403.4.2 Residue. Residues removed during cleaning and  ings, including but not limited to thin paper or plastic and
               debris  contaminated with residue shall be immediately  strippable coatings, are utilized over noncombustible
               removed from the premises and properly disposed.
                                                                     materials to facilitate cleaning operations in spray rooms.
               2403.4.3 Waste  cans.  Approved metal  waste cans
               equipped with self-closing lids shall be provided wherever  2404.3.3 Spray booths.  The design and construction of
                                                                     spray booths shall  be in accordance with Sections
               rags  or waste are impregnated with finishing  material.
               Such rags and waste shall be deposited therein immedi-  2404.3.3.1  through 2404.3.3.6,  Sections 2404.4 through
                                                                     2404.8 and NFPA 33.
               ately after being utilized. The contents of waste cans shall
               be properly disposed of not less than once daily and at the  2404.3.3.1 Construction.  Spray  booths shall be con-
               end of each shift.                                      structed of approved noncombustible materials. Alumi-
                                                                       num shall not be used. Where  walls or ceiling
               2403.4.4 Solvent recycling. Solvent distillation  equip-
               ment used to recycle and clean dirty solvents shall comply  assemblies are constructed of sheet metal, single-skin
               with Section 5705.4.                                    assemblies shall be  not thinner  than 0.0478  inch  (18
                                                                       gage) (1.2 mm) and each sheet of double-skin assem-
                                                                       blies shall be not thinner  than  0.0359  inch  (20 gage)
                               SECTION 2404                            (0.9 mm). Structural sections  of  spray booths are
                             SPRAY FINISHING                           allowed to be sealed with latex-based or similar caulks
                                                                       and sealants.
             2404.1 General. The application of flammable or combusti-
             ble liquids  by  means of spray apparatus in continuous  or  2404.3.3.2 Surfaces. The interior  surfaces of spray
             intermittent processes shall be in accordance with the require-  booths shall be smooth; shall be constructed so as to
             ments of Sections 2403 and 2404.2 through 2404.9.4.       permit the free passage of exhaust air from all parts of
                                                                       the interior, and to facilitate washing and cleaning; and
             2404.2 Location of spray-finishing operations. Spray-fin-  shall be designed to confine residues within the booth.
             ishing operations conducted in buildings used for Group A,  Aluminum shall not be used.
             E, I or R occupancies shall be located in a spray room pro-
             tected with an approved automatic sprinkler system installed  2404.3.3.3 Floor. Combustible floor construction  in
             in accordance with Section 903.3.1.1 and separated vertically  spray booths shall be covered by  approved, noncom-
             and horizontally from the remainder of the building by fire  bustible, nonsparking material, except where combusti-
             barrier walls and horizontal assemblies with not less than a  ble coverings, including but not limited to thin paper or
             1-hour fire-resistance rating in accordance with the Interna-  plastic and  strippable coatings, are utilized over  non-
             tional Building Code. In other occupancies, spray-finishing  combustible materials to facilitate cleaning operations
             operations shall be conducted in a spray room, spray booth or  in spray booths.
             limited spraying space approved for such use.             2404.3.3.4 Means of egress. Means of egress shall be
               Exceptions:                                             provided in accordance with Chapter 10.
                  1. Automobile undercoating spray operations and        Exception: Means of egress doors from premanu-
                    spray-on automotive lining operations conducted in   factured spray booths  shall  be not less than 30
                    areas with approved natural or mechanical ventila-   inches (762 mm) in width by 80 inches (2032 mm)
                    tion shall be exempt from the provisions of Section  in height.

             2018 INTERNATIONAL FIRE CODE ®                                                                      265
  Copyrighted © 2017 by, or licensed to, ICC (ALL RIGHTS RESERVED); licensed to UL, LLC pursuant to License Agreement with ICC. No further reproductions authorized or distribution authorized.
  ANY UNAUTHROIZED REPRODUCTION OR DISTRIBUTION IS A VIOLATION OF THE FEDERAL COPYRIGHT ACT AND THE LICENSE AGREEMENT; AND SUBJECT TO CIVIL AND CRIMINAL PENALTIES THEREUNDER.
   293   294   295   296   297   298   299   300   301   302   303