HAZARDOUS MATERIALS—GENERAL PROVISIONS



           5003.2.7 Liquid-level limit control. Atmospheric tanks    5. Manually activated shutdown controls required
           having a capacity greater than 500 gallons (1893 L) and      by  Section 6403.1.1.1 for  compressed gas sys-
           that contain hazardous material liquids shall be equipped    tems conveying pyrophoric gases.
           with a liquid-level limit control or other approved means  5003.2.9.2 Testing frequency.  The equipment, sys-
           to prevent overfilling of the tank.                     tems and devices listed in Section 5003.2.9.1 shall be
           5003.2.8 Seismic protection. Machinery and equipment    tested at one of the following frequencies:
           utilizing hazardous materials shall be braced and anchored  1. Not less than annually.
           in accordance with the seismic design requirements of the
                                                                     2. In accordance with the approved manufacturer’s
           International Building Code for the seismic design category
           in which the machinery or equipment is classified.           requirements.
           5003.2.9 Testing. The equipment, devices and systems      3. In accordance with approved recognized industry
           listed in Section 5003.2.9.1 shall be tested at the time of  standards.
           installation and at  one of  the  intervals listed in Section  4. In accordance with an approved schedule.
           5003.2.9.2. Records of the tests conducted or maintenance  5003.3 Release of hazardous materials. Hazardous materi-
           performed shall be maintained in accordance with the pro-  als in any quantity shall not be released into a sewer, storm
           visions of Section 108.3.
                                                              drain, ditch, drainage canal, creek, stream, river, lake or tidal
              Exceptions:                                     waterway or on the ground, sidewalk, street, highway or into
                                                              the atmosphere.
                1. Periodic testing  shall  not be required where
                   approved written documentation is provided stat-  Exceptions:
                   ing that  testing will damage the equipment,    1. The  release or emission of hazardous materials is
                   device or system and the equipment, device or     allowed where in compliance with federal, state or
                   system is maintained as specified by the manu-    local governmental agencies, regulations or permits.
                   facturer.
                                                                   2. The release of pesticides is allowed where used in
                2. Periodic testing shall not be required for equip-  accordance with registered label directions.
                   ment, devices and systems that fail in a fail-safe
                   manner.                                         3. The release of fertilizer  and soil amendments  is
                                                                     allowed where used in  accordance with  manufac-
                3. Periodic testing shall not be required for equip-  turer’s specifications.
                   ment, devices and systems that self-diagnose and
                   report trouble. Records of the self-diagnosis and  5003.3.1 Unauthorized discharges. In the event hazard-
                   trouble reporting shall be made available to the  ous materials are released in quantities reportable under
                   fire code official.                           state, federal or local regulations, the  fire code official
                                                                 shall be notified and the following procedures required in
                4. Periodic testing  shall not be required if  system  accordance with Sections 5003.3.1.1 through 5003.3.1.4.
                   activation occurs during the  required test cycle
                   for the components activated during the test    5003.3.1.1 Records. Records of the unauthorized dis-
                   cycle.                                          charge of hazardous materials by the permittee shall be
                                                                   maintained.
                5. Approved maintenance in accordance with Sec-
                   tion 5003.2.6 that is performed  not  less than  5003.3.1.2 Preparation. Provisions shall be made for
                   annually  or in accordance with an  approved    controlling and mitigating unauthorized discharges.
                   schedule shall be allowed to  meet the testing  5003.3.1.3 Control. Where an unauthorized discharge
                   requirements set forth in Sections 5003.2.9.1 and  caused by primary container failure is discovered, the
                   5003.2.9.2.                                     involved  primary container shall be repaired or
              5003.2.9.1 Equipment, devices and systems requir-    removed from service.
              ing testing. The  following equipment, systems and   5003.3.1.4 Responsibility for cleanup. The person,
              devices shall be tested in accordance with  Sections  firm or corporation responsible for an unauthorized dis-
              5003.2.9 and 5003.2.9.2.                             charge shall institute and complete all actions necessary
                1. Gas detection systems, alarms and automatic     to remedy the effects of such unauthorized discharge,
                   emergency shutoff valves required by  Section   whether sudden or gradual, without cost to the jurisdic-
                   6004.2.2.10 for highly toxic and toxic gases.   tion. Where deemed necessary by the fire code official,
                                                                   cleanup can be initiated by the fire department or by an
                2. Limit control systems for liquid level, tempera-  authorized individual or firm. Costs associated with
                   ture and pressure required by Sections 5003.2.7,  such cleanup shall be borne by the owner, operator or
                   5004.8 and 5005.1.4.
                                                                   other person  responsible for the unauthorized dis-
                3. Emergency alarm systems and supervision         charge.
                   required by Sections 5004.9 and 5005.4.4.
                                                              5003.4 Safety Data Sheets. Safety Data Sheets (SDS) shall
                4. Monitoring and supervisory systems required by  be readily available on the premises for hazardous materials
                   Sections 5004.10 and 5005.1.6.             regulated by this chapter. Where a  hazardous substance is