Page 435 - 2018_IFC
P. 435

EXPLOSIVES AND FIREWORKS



              5601.8.1.1 Mass-detonating explosives (Division 1.1,      weight of  explosives for Division  1.1 distance
              1.2 or 1.5). The total net explosive weight of mass-det-  determination. Table 5604.5.2(1) or 5605.3 shall
              onating  explosives (Division 1.1, 1.2  or  1.5) shall be  be used where TNT equivalency is used to estab-
              used. See Table 5604.5.2(1) or Table 5605.3, as appro-    lish the net explosive weight.
              priate.                                                4. For composite pyrotechnic  items  Division 1.1
                Exception:  Where the TNT equivalence of the            and Division 1.3, the sum of the net weights of
                explosive material has been determined, the equiva-     the pyrotechnic composition  and  the  explosives
                lence is allowed to be used to establish the net explo-  involved  shall  be used. See  Tables 5604.5.2(1)
                sive weight.                                            and 5604.5.2(2).
              5601.8.1.2 Nonmass-detonating explosives  (exclud-   5601.8.1.4 Moderate fire—no blast hazards  (Divi-
              ing Division 1.4). Nonmass-detonating  explosives    sion 1.4). For Division 1.4 explosives, the total weight
              (excluding Division 1.4) shall be as follows:        of the explosive material alone is the net weight. The
                                                                   net weight of the explosive material shall be used.
                1. Division 1.3 propellants. The total weight of the
                   propellants alone  shall be the net  explosive
                   weight. The net weight of propellant shall be                SECTION 5602
                   used. See Table 5604.5.2(2).
                                                                                DEFINITIONS
                2. Combinations of bulk metal powder and pyro-  5602.1 Definitions. The following terms are defined in Chap-
                   technic compositions. The sum of the net weights  ter 2:
                   of metal powders and pyrotechnic compositions
                   in the containers shall  be the net  explosive  AMMONIUM NITRATE.
                   weight. See Table 5604.5.2(2).             BARRICADE.
              5601.8.1.3 Combinations  of mass-detonating  and   Artificial barricade.
              nonmass-detonating explosives (excluding Division  Natural barricade.
              1.4).  Combination of  mass-detonating and nonmass-
              detonating explosives (excluding Division 1.4) shall be  BARRICADED.
              as follows:                                     BLAST AREA.
                1. Where Division 1.1  and 1.2  explosives are  BLAST SITE.
                   located in the same site, determine the distance  BLASTER.
                   for the total quantity considered first as 1.1 and
                   then as 1.2. The required distance is the greater of  BLASTING AGENT.
                   the two. Where the Division 1.1 requirements are  BULLET RESISTANT.
                   controlling and the TNT equivalence of the 1.2 is  DETONATING CORD.
                   known, the  TNT equivalent weight of the 1.2
                   items shall be  allowed to be added to the  total  DETONATION.
                   explosive weight of Division 1.1 items to deter-  DETONATOR.
                   mine the net  explosive weight for  Division 1.1  DISCHARGE SITE.
                   distance determination. See Table 5604.5.2(2) or
                   Table 5605.3, as appropriate.              DISPLAY SITE.
                2. Where Division 1.1  and 1.3  explosives are  EXPLOSIVE.
                   located in the same site, determine the distances  High explosive.
                   for the total quantity considered first as 1.1 and  Low explosive.
                   then as 1.3. The required distance is the greater of  Mass-detonating explosives.
                   the two. Where the Division 1.1 requirements are  UN/DOTn Class 1 explosives.
                   controlling and the TNT equivalence of the 1.3 is  Division 1.1.
                   known, the  TNT equivalent weight of the 1.3   Division 1.2.
                   items shall be  allowed to be added to the  total  Division 1.3.
                   explosive weight of Division 1.1 items to deter-  Division 1.4.
                   mine the net  explosive weight for  Division 1.1  Division 1.5.
                   distance determination. See  Table  5604.5.2(1),  Division 1.6.
                   5604.5.2(2) or 5605.3, as appropriate.     EXPLOSIVE MATERIAL.
                3. Where  Division 1.1, 1.2 and 1.3  explosives are  FALLOUT AREA.
                   located in the same site, determine the distances
                   for the total quantity considered first as 1.1, next  FIREWORKS.
                   as 1.2 and finally as 1.3. The required distance is  Fireworks, 1.3G.
                   the greatest of the three. As allowed by Items 1  Fireworks, 1.4G.
                   and 2,  TNT equivalent weights for 1.2 and 1.3  FIREWORKS DISPLAY.
                   items are allowed to be used to determine the net
                                                              HIGHWAY.


         402                                                                        2018 INTERNATIONAL FIRE CODE ®
  Copyrighted © 2017 by, or licensed to, ICC (ALL RIGHTS RESERVED); licensed to UL, LLC pursuant to License Agreement with ICC. No further reproductions authorized or distribution authorized.
  ANY UNAUTHROIZED REPRODUCTION OR DISTRIBUTION IS A VIOLATION OF THE FEDERAL COPYRIGHT ACT AND THE LICENSE AGREEMENT; AND SUBJECT TO CIVIL AND CRIMINAL PENALTIES THEREUNDER.
   430   431   432   433   434   435   436   437   438   439   440