HIGHLY TOXIC AND TOXIC MATERIALS



                    tanks or cylinders are equipped with  approved       both audible and visible and shall provide warning
                    excess flow or reduced flow valves, the worst-case   both inside and outside the area where gas is
                    release shall be determined by the maximum achiev-   detected. The audible alarm shall be distinct from all
                    able flow from the valve as determined by the valve  other alarms.
                    manufacturer or compressed gas supplier. Reduced        Exception:  Signal transmission to a  constantly
                    flow and excess flow valves  shall be  permanently      attended control station is not required where not
                    marked  by the valve  manufacturer to indicate the
                                                                            more than one cylinder of highly toxic or toxic
                    maximum design  flow rate. Such  markings shall         gas is stored.
                    indicate the flow rate for air under normal tempera-
                    ture and pressure.                                   6004.2.2.10.2  Shut off of gas supply. The gas-
                                                                         detection system shall automatically close the shut-
                              TABLE 6004.2.2.7.5                         off valve at the source on gas supply piping and tub-
              RATE OF RELEASE FOR CYLINDERS AND PORTABLE TANKS
                                                                         ing related to the system being monitored for
               VESSEL TYPE  NONLIQUEFIED (minutes)  LIQUEFIED (minutes)  whichever gas is detected.
             Containers             5                30
                                                                            Exception: Automatic shutdown is not required
             Portable tanks        40               240                     for reactors utilized for the production of highly
                                                                            toxic or toxic compressed gases where such reac-
                  6004.2.2.8 Emergency power. Emergency power shall         tors are:
                  be provided for  the following  systems in accordance
                  with Section 604:                                           1. Operated at pressures less than 15 pounds
                                                                                 per square inch gauge (psig) (103.4 kPa).
                    1. Exhaust ventilation system.
                                                                              2. Constantly attended.
                    2. Treatment system.
                                                                              3. Provided with  emergency shutoff valves
                    3. Gas detection system.
                                                                                 that have ready access.
                    4. Smoke detection system.                           6004.2.2.10.3 Valve closure. Automatic closure of
                    5. Temperature control system.                       shutoff valves shall be in accordance with the fol-
                                                                         lowing:
                    6. Fire alarm system.
                                                                            1. Where the gas-detection sampling point initi-
                    7. Emergency alarm system.
                                                                              ating the gas detection system alarm is within
                    6004.2.2.8.1 Fail-safe engineered systems. Emer-          a gas cabinet or exhausted enclosure, the shut-
                    gency  power shall  not be required for mechanical        off  valve in the gas  cabinet  or exhausted
                    exhaust ventilation, treatment systems and tempera-       enclosure for the specific gas detected shall
                    ture control systems where approved fail-safe engi-       automatically close.
                    neered systems are installed.
                                                                            2. Where the gas-detection sampling point initi-
                  6004.2.2.9 Automatic fire detection system—highly           ating the gas detection system alarm is within
                  toxic compressed gases. An approved automatic fire          a gas room and compressed gas containers are
                  detection system  shall be installed in rooms or areas      not in  gas cabinets  or exhausted  enclosures,
                  where highly toxic  compressed gases are stored or          the shutoff valves on all gas lines for the spe-
                  used. Activation of the detection system shall sound a      cific gas detected shall automatically close.
                  local  alarm. The fire detection  system shall  comply    3. Where the gas-detection sampling point initi-
                  with Section 907.                                           ating the gas detection system alarm is within
                  6004.2.2.10 Gas detection system. A gas detection sys-      a piping  distribution  manifold enclosure, the
                  tem complying with Section 916 shall be  provided  to       shutoff valve for the compressed container of
                  detect the presence of gas at or below the PEL or ceiling   specific gas  detected supplying the manifold
                  limit of the gas for which detection is provided. The sys-  shall automatically close.
                  tem shall be capable of monitoring the discharge from     Exception: Where the  gas-detection sampling
                  the treatment system at or below one-half the IDLH limit  point initiating the gas-detection system alarm is
                  and shall initiate a response in accordance with Sections  at a use location or within a gas valve enclosure
                  6004.2.2.10.1 through 6004.2.2.10.3 if the gas detection  of a branch line downstream of a piping distribu-
                  alarm is activated.                                       tion manifold, the shutoff valve in the gas valve
                    Exception: A gas detection system is not required       enclosure for the branch line located in the piping
                    for toxic gases  when the physiological  warning        distribution manifold enclosure shall automati-
                    threshold  level for the gas is at a level  below the   cally close.
                    accepted PEL for the gas.                     6004.3 Outdoor storage and use. The outdoor storage and

                    6004.2.2.10.1 Alarms. The gas detection system  use of highly toxic and toxic compressed gases shall be in
                    shall initiate a local alarm and transmit a signal to a  accordance with Sections 6004.3.1 through 6004.3.4.
                    constantly attended  control station when a  short-  6004.3.1 Applicability. The applicability of regulations
                    term hazard condition is detected. The alarm shall be  governing the outdoor storage and use of highly toxic and