Page 596 - 2018_IFC
P. 596

APPENDIX M

                                  HIGH-RISE BUILDINGS—RETROACTIVE
                                 AUTOMATIC SPRINKLER REQUIREMENT



                            The provisions contained in this appendix are not mandatory unless specifically referenced in
                                          the adopting ordinance or legislation of the jurisdiction.

             User note:
                About this appendix: Appendix M was created with the intent to provide an option for adoption by jurisdictions that choose to require existing
                high-rise buildings to be retrofitted with automatic sprinklers. Modern fire and building codes require complete automatic fire sprinkler protec-
                tion and a variety of other safety features in new high-rise construction. Many older high-rise buildings lack automatic sprinkler protection and
                other basic fire protection features necessary to protect the occupants, emergency responders and the structure itself. Without complete auto-
                matic sprinkler protection, fire departments cannot provide the level of protection that high-rise buildings demand. Existing high-rise buildings
                that are not protected with automatic sprinklers represent a significant hazard to occupants and fire fighters, and can significantly impact a
                community’s infrastructure and economic viability in the event of a fire loss.




                              SECTION M101
                                  SCOPE

             M101.1 Scope. An  automatic sprinkler  system shall be
             installed in all existing high-rise buildings in accordance with
             the requirements and compliance schedule of this appendix.


                              SECTION M102
                            WHERE REQUIRED
             M102.1 High-rise buildings. An automatic sprinkler system
             installed in accordance with Section 903.3.1.1 shall be pro-
             vided throughout existing high-rise buildings.
               Exceptions:
                  1. Airport traffic control towers.
                  2. Open parking structures.
                  3. Group U occupancies.
                  4. Occupancies in Group F-2.


                              SECTION M103
                               COMPLIANCE
             M103.1 Compliance schedule. Building owners shall file a
             compliance schedule with the fire code official not later than
             365 days after receipt of a  written notice of violation. The
             compliance schedule shall not exceed 12 years for an auto-
             matic sprinkler system retrofit.