BOILERS, WATER HEATERS AND PRESSURE VESSELS




             1006.6 Safety and relief valve discharge. Safety and relief  lation of water through the boiler and that are protected
             valve discharge pipes shall be of rigid pipe that is approved  with a flow sensing control.
             for the temperature of the system. High-pressure-steam safety  1007.2 Operation. Low-water cutoff controls and flow sens-
             valves shall be vented to the outside of the structure. The dis-  ing controls required by Section 1007.1 shall automatically
             charge piping  serving pressure relief  valves,  temperature  stop the  combustion operation of  the  appliance when  the
             relief valves and combinations of such valves shall:  water level drops below the lowest safe water level as estab-
                1. Not be directly connected to the drainage system.  lished by the manufacturer or when water circulation stops,
                                                                  respectively.
                2. Discharge  through an  air break located  in the same
                   room as the appliance.
                3. Not be smaller than the diameter of the outlet of the            SECTION 1008
                   valve served and shall discharge full size to the air      BOTTOM BLOWOFF VALVE
                   break.
                                                                  1008.1 General. Steam boilers shall be equipped with bottom
                4. Serve a single relief device and shall not connect to  blowoff valve(s). The valve(s) shall be installed in the open-
                   piping serving any other relief device or equipment.  ing provided on the boiler. The minimum size of the valve(s)
                5. Discharge to the floor, to the pan serving the boiler or  and associated piping shall be the size specified by the boiler
                   storage tank, to a waste receptor or to the outdoors.  manufacturer or the size of the boiler blowoff-valve opening.
                                                                  Where  the  maximum allowable working pressure of  the
                6. Discharge in a manner that does not cause personal
                   injury or structural damage.                   boiler exceeds  100 psig (689  kPa), two bottom  blowoff
                                                                  valves shall be provided consisting of either two slow-open-
                7. Discharge to a  termination  point  that is  readily  ing valves in series or one quick-opening valve and one slow-
                   observable by the building occupants.          opening  valve in series,  with the quick-opening  valve
                8. Not be trapped.                                installed closest to the boiler.
                9. Be installed so as to flow by gravity.         1008.2 Discharge. Blowoff valves shall discharge to a safe
                                                                  place of disposal. Where discharging to the drainage system,
               10. Not terminate more than 6 inches (152 mm) above the  the installation shall conform to the International Plumbing
                   floor or waste receptor.
                                                                  Code.
               11. Not have a threaded connection at the end of such pip-
                   ing.
               12. Not have valves or tee fittings.                                 SECTION 1009
               13. Be constructed of those materials listed  in Section  HOT WATER BOILER EXPANSION TANK
                   605.4 of the International Plumbing Code or materi-  1009.1  Where  required.  An expansion tank shall be
                   als tested, rated and approved for such use in accor-  installed in every hot water system. For multiple boiler instal-
                   dance with ASME A112.4.1.                      lations, not less than one expansion tank is required. Expan-
             1006.7 Boiler safety devices. Boilers shall be equipped with  sion tanks shall be of the closed or open type. Tanks shall be
             controls and limit devices as required by the manufacturer’s  rated for the pressure of the hot water system.
             installation instructions and the conditions of the listing.  Exception: Expansion tanks shall not be required in the
             1006.8  Electrical  requirements. The  power  supply to the  collector loop of drain-back systems.
             electrical control system shall be from a two-wire branch cir-  1009.2  Closed-type  expansion  tanks. Closed-type  expan-
             cuit that has a grounded conductor, or from an isolation trans-  sion tanks shall be installed in accordance with the manufac-
             former with a two-wire secondary. Where an isolation  turer’s instructions. Expansion tanks for systems designed to
             transformer is provided, one conductor  of  the secondary  have an operating pressure in excess of 30 psi (207 kPa) shall
             winding shall be grounded. Control voltage shall not exceed  be constructed and certified in accordance with the ASME
             150 volts nominal, line to line. Control and limit devices shall  Boiler and Pressure Vessel Code. The size of the tank shall
             interrupt the ungrounded side of the circuit. A means of man-  be based on the capacity of the hot-water-heating system. The
             ually disconnecting the control circuit shall be provided and  minimum size of the tank shall be determined in accordance
             controls shall be arranged so that when deenergized, the  with the following equation where all necessary information
             burner shall be inoperative. Such disconnecting means shall  is known:
             be capable of being locked in the off position and shall be  (  0.00041T –  0.0466)  V
             provided with ready access.                          V =  -------------------------------------------------------- s  (Equation 10-1)
                                                                    t
                                                                              P a    P a
                                                                                   -----
                                                                              ----- –   P   o
                                                                             P 
                                                                              f
                               SECTION 1007
                       BOILER LOW-WATER CUTOFF
             1007.1 General. Steam and hot water boilers shall be pro-
             tected with a low-water cutoff control.
               Exception: A low-water cutoff is not required for coil-
               type and water-tube-type boilers that require forced circu-

             2018 INTERNATIONAL MECHANICAL CODE                                                                  97