Page 132 - 2018_IMC
P. 132

HYDRONIC PIPING




                  tration into the outlet is of the correct depth. For inspec-  with tubing that has an ethylene vinyl alcohol copolymer
                                                        1
                  tion purposes, a second dimple shall be placed  /  inch  (EVOH) oxygen barrier layer.
                                                          4
                  (6.4  mm) above  the first  dimple. Dimples shall  be  1203.10 PVC plastic pipe. Joints between PVC plastic pipe
                  aligned with the tube run.
                                                                  and fittings shall be solvent-cemented or threaded joints con-
                  1203.3.8.2 Brazed joints. Mechanically formed tee fit-  forming to Section 1203.3.
                  tings  shall be brazed in accordance with  Section  1203.11 Steel pipe. Joints between steel pipe or fittings shall
                  1203.3.1.                                       be mechanical joints that are made with an approved elasto-
             1203.4 ABS plastic pipe. Joints between ABS plastic pipe or  meric seal, or shall be threaded or welded joints conforming
             fittings shall be solvent-cemented or threaded joints conform-  to Section 1203.3.
             ing to Section 1203.3.                               1203.12 Steel tubing. Joints between steel tubing or fittings

             1203.5 Copper or copper-alloy pipe. Joints between copper  shall be mechanical or welded joints conforming to Section
             or copper-alloy pipe or fittings shall be brazed, mechanical,  1203.3.
             soldered, threaded or welded  joints conforming to  Section  1203.13  Polypropylene  (PP)  plastic. Joints between PP
             1203.3.                                              plastic pipe and fittings shall comply with Sections 1203.13.1
                                                                  and 1203.13.2.
             1203.6 Copper or copper-alloy tubing. Joints between cop-
             per or copper-alloy tubing or fittings shall be brazed, mechan-  1203.13.1 Heat-fusion joints. Heat-fusion joints for poly-
             ical or soldered joints conforming to Section 1203.3, flared  propylene  (PP) pipe and tubing joints shall be installed
             joints  conforming to  Section 1203.6.1, push-fit joints con-  with  socket-type heat-fused polypropylene fittings,  elec-
             forming to Section 1203.6.2 or press-connect joints conform-  tro-fusion polypropylene fittings or by butt fusion. Joint
             ing to Section 1203.6.3.                                surfaces shall be clean and free from moisture. The joint
                                                                     shall  be  undisturbed  until  cool. Joints shall be made in
               1203.6.1 Flared joints. Flared joints shall be made by a
               tool designed for that operation.                     accordance with ASTM F2389.
                                                                     1203.13.2  Mechanical  and  compression  sleeve  joints.
               1203.6.2 Push-fit joints. Push-fit joints shall be installed  Mechanical and compression sleeve joints shall be
               in accordance with the manufacturer’s instructions.
                                                                     installed  in accordance with the manufacturer’s instruc-
               1203.6.3 Press-connect joints. Press-connect joints shall  tions.
               be installed in accordance with the manufacturer’s instruc-  1203.14 Raised temperature polyethylene (PE-RT) plastic
               tions.
                                                                  tubing. Joints between raised temperature polyethylene tub-
             1203.7  CPVC  plastic  pipe. Joints between CPVC plastic  ing and fittings shall conform to Sections 1203.14.1 through
             pipe or fittings shall be solvent-cemented or threaded joints  1203.14.3. Mechanical joints  shall conform  to Section
             conforming to Section 1203.3.                        1203.3.
             1203.8  Polybutylene  plastic  pipe  and  tubing. Joints  1203.14.1  Compression-type  fittings. Where  compres-
             between polybutylene plastic pipe and tubing or fittings shall  sion-type fittings include inserts and ferrules or O-rings,
             be mechanical joints conforming to Section 1203.3 or heat-  the fittings shall be installed without omitting the inserts
             fusion joints conforming to Section 1203.8.1.           and ferrules or O-rings.
               1203.8.1 Heat-fusion joints. Joints shall be of the socket-  1203.14.2 PE-RT-to-metal connections. Solder joints in
               fusion or butt-fusion type. Joint surfaces shall be clean and  a metal pipe shall not occur within 18 inches (457 mm) of
               free  of moisture. Joint  surfaces shall be heated to melt  a transition from such metal pipe to PE-RT pipe.
               temperatures and joined. The joint shall be undisturbed
                                                                     1203.14.3 Push-fit joints. Push-fit joints that create a seal
               until cool. Joints shall be made in accordance with ASTM  on the outside diameter of  the tubing shall  not  be  used
               D3309.                                                with tubing that has an ethylene vinyl alcohol copolymer
             1203.9  Cross-linked  polyethylene  (PEX)  plastic  tubing.  (EVOH) oxygen barrier layer.
             Joints between cross-linked polyethylene plastic tubing and  1203.15  Polyethylene/aluminum/polyethylene  (PE-AL-
             fittings shall conform to Sections 1203.9.1 through 1203.9.3.  PE) pressure pipe. Joints between polyethylene/aluminum/
             Mechanical joints shall conform to Section 1203.3.
                                                                  polyethylene pressure pipe and fittings shall conform to Sec-
               1203.9.1  Compression-type  fittings. Where compres-  tions 1203.15.1 and 1203.15.2. Mechanical joints shall com-
               sion-type fittings include inserts and ferrules or O-rings,  ply with Section 1203.3.
               the fittings shall be installed without omitting the inserts
                                                                     1203.15.1  Compression-type  fittings. Where  compres-
               and ferrules or O-rings.
                                                                     sion-type fittings include inserts and ferrules or O-rings,
               1203.9.2 Plastic-to-metal connections. Soldering on the  the fittings shall be installed without omitting the inserts
               metal portion  of the system  shall be performed not  less  and ferrules or O-rings.
               than 18 inches (457 mm) from a plastic-to-metal adapter in
                                                                     1203.15.2  PE-AL-PE-to-metal  connections. Solder
               the same water line.
                                                                     joints in a metal pipe shall not occur within 18 inches (457
               1203.9.3 Push-fit joints. Push-fit joints that create a seal  mm) of a  transition from  such metal  pipe  to PE-AL-PE
               on the outside diameter of the tubing shall not be used  pipe.