Page 136 - 2018_IFGC
P. 136

CHAPTER 6

                                              SPECIFIC APPLIANCES




             User note:
                                                                         
                About this chapter: Similar to Chapter 9 of the International Mechanical Code , Chapter 6 of this code addresses specific types of appli-
                ances in detail. Requirements include listing and labeling, installation, location, clearances, venting and exhausting, controls, support and
                combustion and ventilation air.



                            SECTION 601 (IFGC)                    604.2 Access. Panels,  grilles and  access doors that  are
                                 GENERAL                          required to be removed for normal servicing operations shall
                                                                  not be attached to the building.
             601.1 Scope. This chapter shall govern the approval, design,
             installation, construction, maintenance, alteration and repair
             of  the appliances and  equipment specifically  identified          SECTION 605 (IFGC)
             herein.
                                                                         VENTED GAS FIREPLACE HEATERS
                                                                  605.1 General. Vented gas fireplace heaters shall be installed
                            SECTION 602 (IFGC)                    in accordance with the manufacturer’s instructions, shall be
                        DECORATIVE APPLIANCES                     tested in accordance with ANSI Z21.88/CSA 2.33 and shall
                    FOR INSTALLATION IN FIREPLACES                be designed and equipped as specified in Section 602.2.
             602.1 General. Decorative appliances  for installation in
             approved solid  fuel-burning fireplaces  shall be tested  in        SECTION 606 (IFGC)
             accordance with  ANSI Z21.60/CSA 6.26 and shall be          INCINERATORS AND CREMATORIES
             installed in accordance with the manufacturer’s instructions.
             Manually lighted natural gas decorative appliances shall be  606.1 General. Incinerators  and  crematories shall be
             tested in accordance with ANSI Z21.84.               installed in accordance with the manufacturer’s instructions.
             602.2 Flame  safeguard device. Decorative appliances for
             installation in  approved solid fuel-burning  fireplaces, with      SECTION 607 (IFGC)
             the exception  of those  tested in accordance with  ANSI  COMMERCIAL-INDUSTRIAL INCINERATORS
             Z21.84, shall utilize a direct ignition device, an ignitor or a
             pilot flame to ignite the fuel at the main burner, and shall be  607.1 Incinerators, commercial-industrial. Commsercial-
             equipped with a flame safeguard device. The flame safeguard  industrial-type incinerators shall be constructed and installed
             device shall automatically shut off the fuel supply to a main  in accordance with NFPA 82.
             burner or group of burners  when  the means  of  ignition of
             such burners becomes inoperative.
                                                                                 SECTION 608 (IFGC)
             602.3 Prohibited installations. Decorative appliances for        VENTED WALL FURNACES
             installation in fireplaces shall not be installed where prohib-
             ited by Section 303.3.                               608.1 General. Vented wall furnaces shall be tested in accor-
                                                                  dance with ANSI Z21.86/CSA 2.32 and shall be installed in
                                                                  accordance with the manufacturer’s instructions.
                            SECTION 603 (IFGC)                    608.2 Venting.  Vented wall furnaces  shall be vented  in
                              LOG LIGHTERS                        accordance with Section 503.
             603.1 General. Log lighters  shall  be tested in accordance  608.3 Location. Vented wall furnaces shall be located so as
             with CSA 8 and installed in accordance with the manufac-  not to cause a fire hazard to walls, floors, combustible fur-
             turer’s instructions.                                nishings or doors. Vented wall furnaces installed between
                                                                  bathrooms and adjoining rooms shall not circulate air from
                                                                  bathrooms to other parts of the building.
                            SECTION 604 (IFGC)
                        VENTED GAS FIREPLACES                     608.4 Door swing. Vented wall furnaces shall be located so
                        (DECORATIVE APPLIANCES)                   that a door cannot swing within 12 inches (305 mm) of an air
                                                                  inlet or air outlet of such furnace measured at right angles to
             604.1 General. Vented gas fireplaces shall be tested in accor-  the opening. Doorstops or door closers shall not be installed
             dance  with ANSI Z21.50/CSA 2.22, shall be installed in  to obtain this clearance.
             accordance with the manufacturer’s instructions and shall be  608.5 Ducts prohibited. Ducts shall not be attached to wall
             designed and equipped as specified in Section 602.2.
                                                                  furnaces. Casing extension boots shall not be installed unless
                                                                  listed as part of the appliance.


             2018 INTERNATIONAL FUEL GAS CODE ®                                                                  123
  Copyrighted © 2017 by, or licensed to, ICC (ALL RIGHTS RESERVED); licensed to UL, LLC pursuant to License Agreement with ICC. No further reproductions authorized or distribution authorized.
  ANY UNAUTHROIZED REPRODUCTION OR DISTRIBUTION IS A VIOLATION OF THE FEDERAL COPYRIGHT ACT AND THE LICENSE AGREEMENT; AND SUBJECT TO CIVIL AND CRIMINAL PENALTIES THEREUNDER.