Page 136 - 2018_IFGC
P. 136
CHAPTER 6
SPECIFIC APPLIANCES
User note:
About this chapter: Similar to Chapter 9 of the International Mechanical Code , Chapter 6 of this code addresses specific types of appli-
ances in detail. Requirements include listing and labeling, installation, location, clearances, venting and exhausting, controls, support and
combustion and ventilation air.
SECTION 601 (IFGC) 604.2 Access. Panels, grilles and access doors that are
GENERAL required to be removed for normal servicing operations shall
not be attached to the building.
601.1 Scope. This chapter shall govern the approval, design,
installation, construction, maintenance, alteration and repair
of the appliances and equipment specifically identified SECTION 605 (IFGC)
herein.
VENTED GAS FIREPLACE HEATERS
605.1 General. Vented gas fireplace heaters shall be installed
SECTION 602 (IFGC) in accordance with the manufacturer’s instructions, shall be
DECORATIVE APPLIANCES tested in accordance with ANSI Z21.88/CSA 2.33 and shall
FOR INSTALLATION IN FIREPLACES be designed and equipped as specified in Section 602.2.
602.1 General. Decorative appliances for installation in
approved solid fuel-burning fireplaces shall be tested in SECTION 606 (IFGC)
accordance with ANSI Z21.60/CSA 6.26 and shall be INCINERATORS AND CREMATORIES
installed in accordance with the manufacturer’s instructions.
Manually lighted natural gas decorative appliances shall be 606.1 General. Incinerators and crematories shall be
tested in accordance with ANSI Z21.84. installed in accordance with the manufacturer’s instructions.
602.2 Flame safeguard device. Decorative appliances for
installation in approved solid fuel-burning fireplaces, with SECTION 607 (IFGC)
the exception of those tested in accordance with ANSI COMMERCIAL-INDUSTRIAL INCINERATORS
Z21.84, shall utilize a direct ignition device, an ignitor or a
pilot flame to ignite the fuel at the main burner, and shall be 607.1 Incinerators, commercial-industrial. Commsercial-
equipped with a flame safeguard device. The flame safeguard industrial-type incinerators shall be constructed and installed
device shall automatically shut off the fuel supply to a main in accordance with NFPA 82.
burner or group of burners when the means of ignition of
such burners becomes inoperative.
SECTION 608 (IFGC)
602.3 Prohibited installations. Decorative appliances for VENTED WALL FURNACES
installation in fireplaces shall not be installed where prohib-
ited by Section 303.3. 608.1 General. Vented wall furnaces shall be tested in accor-
dance with ANSI Z21.86/CSA 2.32 and shall be installed in
accordance with the manufacturer’s instructions.
SECTION 603 (IFGC) 608.2 Venting. Vented wall furnaces shall be vented in
LOG LIGHTERS accordance with Section 503.
603.1 General. Log lighters shall be tested in accordance 608.3 Location. Vented wall furnaces shall be located so as
with CSA 8 and installed in accordance with the manufac- not to cause a fire hazard to walls, floors, combustible fur-
turer’s instructions. nishings or doors. Vented wall furnaces installed between
bathrooms and adjoining rooms shall not circulate air from
bathrooms to other parts of the building.
SECTION 604 (IFGC)
VENTED GAS FIREPLACES 608.4 Door swing. Vented wall furnaces shall be located so
(DECORATIVE APPLIANCES) that a door cannot swing within 12 inches (305 mm) of an air
inlet or air outlet of such furnace measured at right angles to
604.1 General. Vented gas fireplaces shall be tested in accor- the opening. Doorstops or door closers shall not be installed
dance with ANSI Z21.50/CSA 2.22, shall be installed in to obtain this clearance.
accordance with the manufacturer’s instructions and shall be 608.5 Ducts prohibited. Ducts shall not be attached to wall
designed and equipped as specified in Section 602.2.
furnaces. Casing extension boots shall not be installed unless
listed as part of the appliance.
2018 INTERNATIONAL FUEL GAS CODE ® 123
Copyrighted © 2017 by, or licensed to, ICC (ALL RIGHTS RESERVED); licensed to UL, LLC pursuant to License Agreement with ICC. No further reproductions authorized or distribution authorized.
ANY UNAUTHROIZED REPRODUCTION OR DISTRIBUTION IS A VIOLATION OF THE FEDERAL COPYRIGHT ACT AND THE LICENSE AGREEMENT; AND SUBJECT TO CIVIL AND CRIMINAL PENALTIES THEREUNDER.