Page 169 - 2018_IFGC
P. 169

APPENDIX B































         Example: Manifolded Common Vent Connector LM shall be not greater than
         18 times the common vent connector manifold inside diameter; i.e., a 4-inch
         (102 mm) inside diameter common vent connector manifold shall not exceed   Vent connector size depends on:    Common vent size depends on:
         72 inches (1829 mm) in length (see Section 504.3.4).       • Input            • Combined inputs
         Note: This is an illustration of a typical manifolded vent connector. Different        • Rise  • Available total height “H”
         appliance, vent connector, or common vent types are possible. Consult        • Available total height “H”  • Table 504.3(1) common vent
         Section 502.3.                                            • Table 504.3(1) connectors
                             FIGURE B-11                                          FIGURE B-13
               USE OF MANIFOLD COMMON VENT CONNECTOR                MULTISTORY GAS VENT DESIGN PROCEDURE
                                                                         FOR EACH SEGMENT OF SYSTEM




                                                                     USE INDIVIDUAL        LISTED CAP
                                                                     VENT FOR
                                                                     TOP FLOOR
                                                                     APPLIANCE IF
                                                                     CONNECTOR
                                                                     REQUIREMENT FOR
                                                                     RISE OF TOTAL         USE AVAILABLE TOTAL HEIGHT FOR TOP
                                                                     HEIGHT CANNOT         FLOOR APPLIANCE AND COMBINED INPUT
                                                                     BE MET                OF ALL APPLIANCES ON COMMON VENT
                                                                                AVAILABLE TOTAL
                                                                                HEIGHT FOR TOP
                                                                                FLOOR APPLIANCE
                                                                                           THIRD INTERCONNECTION TEE*
                                                               USE VENT CONNECTOR TABLE
                                                                                           AVAILABLE TOTAL HEIGHT FOR THIRD
                                                                                           FLOOR APPLIANCE
                                                                                RISE
                                                                                           AVAILABLE TOTAL HEIGHT FOR THIRD FLOOR
                                                                  TOP FLOOR APPLIANCE      APPLIANCE AND COMBINED INPUT OF THREE
                                                                                           APPLIANCES (IF TOP FLOOR APPLIANCE IS NOT
                                                                                           CONNECTED, MEASURED TOTAL HEIGHT TO
                                                                              4            VENT TOP)
                                                               USE VENT CONNECTOR TABLE    SECOND INTERCONNECTION TEE*
                                                                                RISE       USE AVAILABLE TOTAL HEIGHT FOR SECOND
                                                                                           FLOOR APPLIANCE AND COMBINED HEAT INPUT
                                                                                           OF TWO APPLIANCES
                                                                 THIRD FLOOR APPLIANCE
                                                                                           AVAILABLE TOTAL HEIGHT FOR SECOND
                                                                              3            FLOOR APPLIANCE
                                                                                           FIRST INTERCONNECTION TEE*
                                                               USE VENT CONNECTOR TABLE
                                                                                RISE
                                                               SECOND FLOOR APPLIANCE
                                                                                          DESIGN VENT CONNECTOR FOR
                                                                                          FIRST FLOOR APPLIANCE AS AN
                                                                              2           INDIVIDUAL VENT OF THIS TOTAL
                                                                                          HEIGHT FOR INPUT OF FIRST
                                                                                          FLOOR APPLIANCE
                                                               USE VENT CONNECTOR TABLE
                                                                 FIRST FLOOR APPLIANCE
                                                                                           TEE WITH CAP OPTIONAL
                                                                              1    * EACH INTERCONNECTION TEE IS SAME SIZE AS
                                                                                   THE SEGMENT OF COMMON VENT DIRECTLY ABOVE
         Example: Offset Common Vent
         Note: This is an illustration of a typical offset vent. Different appliance, vent   Principles of design of multistory vents using vent connector and common
         connector, or vent types are possible. Consult Sections 504.2 and 504.3.  vent design tables (see Sections 504.3.11 through 504.3.17).
                             FIGURE B-12                                          FIGURE B-14
                     USE OF OFFSET COMMON VENT                             MULTISTORY VENT SYSTEMS
         156                                                                    2018 INTERNATIONAL FUEL GAS CODE ®