Page 29 - 2018_IFGC
P. 29

DEFINITIONS


         of the service meter assembly, such valve shall be considered  sure.  For undiluted liquefied petroleum gas systems, the reg-
         to be downstream of the point of delivery. For undiluted liq-  ulator located upstream from all line gas pressure regulators,
         uefied petroleum gas systems, the point of delivery shall be  where installed, and downstream from any first stage or a
         considered to be the outlet of the service pressure regulator,  high pressure regulator in the system.
         exclusive of line gas regulators, in the system.     RELIEF OPENING. The opening provided in a draft hood
         PORTABLE FUEL CELL APPLIANCE. A fuel cell gen-       to permit the ready escape to the atmosphere of the flue prod-
         erator of electricity, which is not fixed in place. A portable  ucts from the draft hood in the event of no draft, back draft or
         fuel cell appliance utilizes a cord and plug connection to a  stoppage beyond the draft hood, and to permit air into the
         grid-isolated load and has an integral fuel supply.  draft hood in the event of a strong chimney updraft.
         PRESSURE DROP. The loss in pressure due to friction or  RELIEF VALVE (DEVICE). A  safety valve  designed to
         obstruction in pipes, valves, fittings, regulators and burners.  forestall the development of a dangerous condition by reliev-
         PRESSURE TEST. An operation performed to verify the  ing either pressure, temperature or vacuum in the hot water
         gas-tight integrity of gas piping following its installation or  supply system.
         modification.                                        RELIEF VALVE,  PRESSURE. An automatic valve  that
         PURGE. To free a gas conduit of air or gas, or a mixture of  opens and closes a relief vent, depending on whether the pres-
         gas and air.                                         sure is above or below a predetermined value.
         QUICK-DISCONNECT DEVICE. A hand-operated device      RELIEF VALVE, TEMPERATURE.
         that provides a means for connecting and disconnecting an  Manual reset type. A valve that automatically opens a
         appliance or an appliance connector to a gas supply and that  relief vent at a predetermined temperature and that must be
         is equipped with an automatic means to shut off the gas sup-  manually returned to the closed position.
         ply when the device is disconnected.
                                                                 Reseating or self-closing type. An automatic valve that
         [M] READY ACCESS (TO). That which enables a device,     opens and closes a relief vent, depending on whether the
         appliance or  equipment to be directly  reached,  without  temperature is above or below a predetermined value.
         requiring the removal or movement of any panel, door or sim-  RELIEF VALVE, VACUUM. A valve  that  automatically
         ilar obstruction (see “Access”).
                                                              opens and closes a vent for relieving a vacuum within the hot
         [A] REGISTERED DESIGN PROFESSIONAL. An indi-         water supply system, depending on whether the vacuum is
         vidual who is registered or licensed to practice their respec-  above or below a predetermined value.
         tive design profession  as  defined by the  statutory  RISER, GAS. A vertical pipe supplying fuel gas.
         requirements of the professional registration laws of the state
         or jurisdiction in which the project is to be constructed.  ROOM HEATER, UNVENTED. See “Unvented room
                                                              heater.”
         REGULATOR. A device for controlling and maintaining a
         uniform supply pressure, either pounds-to-inches water col-  ROOM HEATER, VENTED. A free-standing heating unit
         umn (MP regulator) or inches-to-inches water column (appli-  used for direct heating of the space in and adjacent to that in
         ance regulator).                                     which the unit is located (see “Vented room heater”).
                                                              SAFETY SHUTOFF DEVICE. See “Flame safeguard.”
         REGULATOR, GAS APPLIANCE. A pressure regulator
         for controlling pressure to the manifold of the appliance.  [BF] SHAFT. An enclosed space extending through one or
                                                             more stories of a  building, connecting vertical  openings  in
         REGULATOR, LINE GAS PRESSURE. A device placed
         in a gas line between the service pressure regulator and the  successive floors, or floors and the roof.
         appliance for controlling, maintaining or reducing the pres-  [A] SLEEPING UNIT. A room or space in which people
         sure in that portion of the piping system downstream of the  sleep, which can also include permanent provisions for liv-
         device.                                              ing, eating and either sanitation or kitchen facilities, but not
                                                              both. Such rooms and spaces that are also part of a dwelling
         REGULATOR, MEDIUM-PRESSURE (MP Regulator).
         A line pressure regulator that reduces gas pressure from the  unit are not sleeping units.
         range of greater than 0.5 psig (3.4 kPa) and less than or equal  SPECIFIC GRAVITY. As applied to gas, specific gravity is
         to 5 psig (34.5 kPa) to a lower pressure.            the ratio of the weight of a given volume to that of the same
                                                              volume of air, both measured under the same condition.
         REGULATOR, MONITORING. A pressure regulator set
         in series with another pressure regulator for the purpose of  STATIONARY FUEL  CELL POWER  PLANT. A self-
         automatically taking control of the pressure downstream of  contained package or factory-matched packages that consti-
         the monitored regulator when that pressure exceeds a set min-  tute an automatically operated assembly of integrated sys-
         imum.                                                tems for generating electrical energy and recoverable thermal
                                                              energy that is permanently connected and fixed in place.
         REGULATOR, PRESSURE. A device placed in a gas line
         for reducing, controlling and maintaining the pressure in that  THERMOSTAT.
         portion of the piping system downstream of the device.  Electric switch type. A device that senses changes in tem-
         REGULATOR, SERIES. A pressure regulator in series with  perature and controls electrically, by means of separate
         one or more other pressure regulators.                  components, the flow of gas to the burner(s) to maintain
                                                                 selected temperatures.
         REGULATOR, SERVICE  PRESSURE. For natural gas
         systems, a device installed  by the serving gas supplier to  [P] THIRD-PARTY CERTIFICATION AGENCY.  An
         reduce and limit the service line pressure to delivery pres-  approved agency operating a product or material certification


         16                                                                     2018 INTERNATIONAL FUEL GAS CODE ®
  Copyrighted © 2017 by, or licensed to, ICC (ALL RIGHTS RESERVED); licensed to UL, LLC pursuant to License Agreement with ICC. No further reproductions authorized or distribution authorized.
  ANY UNAUTHROIZED REPRODUCTION OR DISTRIBUTION IS A VIOLATION OF THE FEDERAL COPYRIGHT ACT AND THE LICENSE AGREEMENT; AND SUBJECT TO CIVIL AND CRIMINAL PENALTIES THEREUNDER.
   24   25   26   27   28   29   30   31   32   33   34