GAS PIPING INSTALLATIONS




                                10,100  7,160  5,850  5,070  4,540  4,140  3,590  3,210  2,930  2,720  2,540  2,400  2,280  1,860  1,610  1,440  1,320
                            62






            Natural   Less than 2 psi   3.0 in. w.c.  0.60   60  8,800  6,270  5,140  4,460  4,000  3,660  3,180  2,850  2,600  2,420  2,260  2,140  2,030  1,660  1,440  1,290  1,180


            Gas             48  5,010  3,560  2,910  2,530  2,270  2,070  1,800  1,610  1,470  1,360  1,280  1,200  1,140  936  812  728  665
              Inlet Pressure  Pressure Drop  Specific Gravity  46  4,430  3,200  2,540  2,200  1,960  1,790  1,550  1,380  1,260  1,170  1,090  1,030  974  793  686  613  559








                            39  2,423  1,740  1,433  1,249  1,123  1,029  897  806  739  686  644  609  579  477  415  373  342



                            37  2,140  1,530  1,250  1,090  978  895  778  698  639  593  555  524  498  409  355  319  234




                            31 Capacity in Cubic Feet of Gas Per Hour  1,370  958  778  672  599  546  471  421  383  355  331  311  295  240  207  184  168



                      INTENDED USE: INITIAL SUPPLY PRESSURE OF 8.0-INCH W.C. OR GREATER  TUBE SIZE (EHD)   30  1,180  828  673  580  518  471  407  363  330  306  285  268  254  206  178  159  144 Table includes losses for four 90-degree bends and two end fittings. Tubing runs with larger numbers of bends or fittings shall be increased by an equivalent length of tubing to the following equation:  EHD—Equivalent Hydraulic Diameter, which is a measure of the relative hydraulic efficien



                            25  649  462  379  329  295  270  234  210  192  178  167  157  149  122  106  95  87



            TABLE 402.4(16) CORRUGATED STAINLESS STEEL TUBING (CSST)  23  19  529  327  380  231  313  189  273  164  245  147  225  134  196  116  176  104  161  95  150  88  141  82  133  77  126  73  104  60  91  52  82  46  75  42 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound per square inch = 6.895 kPa, 1-inch water column = 0.2488 kPa,








                            18  277  197  161  140  125  115  100  89  82  76  71  67  63  52  45  40  37 1 British thermal unit per hour = 0.2931 W, 1 cubic foot per hour = 0.0283 m 3 /h, 1 degree = 0.01745 rad. L = 1.3n where L is additional length (feet) of tubing and n is the number of additional fittings or bends.


                            15  160  112  90  78  69  63  54  48  44  41  38  36  34  27  23  21  19



                            13  120  83  67  57  51  46  39  35  32  29  27  26  24  19  17  15  13  Table entries have been rounded to three significant digits.





                          Flow  Designation  Length (ft)  5  10  15  20  25  30  40  50  60  70  80  90  100  150  200  250  300

                                                                            For SI:  Notes:  1.  2.  3.