WALL CONSTRUCTION


                R602.10.2.2.1 Location of braced wall  panels in  at the end of a braced wall line shall contribute its pro-
                Seismic Design Categories D , D  and D . Braced  jected length for only one of the braced wall lines at the
                                            1
                                         0
                                                   2
               wall panels shall be located at each end of a braced  projected corner.
              wall                                     line.       Exception: The length of wall bracing for dwellings in
                   Exception:  Braced  wall  panels  constructed  of  Seismic Design Categories D , D and D  with stone or
                                                                                           0
                                                                                                    2
                                                                                              1
                   Method  WSP  or  BV-WSP  and  continuous        masonry  veneer  installed  in  accordance  with  Section
                   sheathing  methods  as  specified  in  Section  R703.8 and exceeding the first-story height shall be in
                   R602.10.4 shall be permitted to begin not more  accordance with Section R602.10.6.5.
                   than  10  feet  (3048  mm)  from  each  end  of  a  R602.10.4 Construction methods for braced wall pan-
                   braced wall line provided that each end complies  els.  Intermittent  and  continuously  sheathed  braced wall
                   with one of the following:                    panels shall be constructed in accordance with this section
                     1. A minimum 24-inch-wide (610 mm) panel    and the methods listed in Table R602.10.4.
                       for  Methods  WSP,  CS-WSP,  CS-G  and      R602.10.4.1  Mixing  methods.  Mixing  of  bracing
                       CS-PF is applied to each side of the build-  methods shall be permitted as follows:
                       ing corner as shown in End Condition 4 of     1. Mixing  intermittent  bracing  and  continuous
                       Figure R602.10.7.                                sheathing  methods  from  story  to  story  shall  be
                     2. The end of each braced wall panel closest       permitted.
                       to the end of the braced wall line shall have  2. Mixing  intermittent  bracing  methods  from
                       an 1,800 lb (8 kN) hold-down device fas-         braced wall line to braced wall line within a story
                       tened to the stud at the edge of the braced      shall  be  permitted.  In  regions  within  Seismic
                       wall panel closest to the corner and to the      Design Categories A, B and C where the ultimate
                       foundation  or  framing  below  as  shown  in    design  wind  speed  is  less  than  or  equal  to  130
                       End Condition 5 of Figure R602.10.7.             mph (58m/s), mixing of intermittent bracing and
              R602.10.2.3 Minimum number of braced wall pan-            continuous sheathing methods from braced wall
              els.  Braced wall  lines  with  a  length  of  16  feet   line  to  braced  wall  line  within  a  story  shall  be
              (4877 mm) or less shall have not less than two braced     permitted.
              wall panels  of  any  length  or  one  braced wall panel  3. Mixing  intermittent  bracing  methods  along  a
              equal to 48 inches (1219 mm) or more.  Braced wall        braced wall line  shall  be  permitted  in  Seismic
              lines greater than 16 feet (4877 mm) shall have not less
              than two braced wall panels.                              Design Categories A and B, and detached dwell-
                                                                        ings in Seismic Design Category C, provided that
           R602.10.3  Required  length  of  bracing.  The  required     the length of required bracing in accordance with
           length  of  bracing  along  each  braced wall line  shall  be  Table R602.10.3(1) or R602.10.3(3) is the highest
           determined as follows:                                       value of all intermittent bracing methods used.
              1. All buildings in Seismic Design Categories A and B  4. Mixing  of  continuous  sheathing  methods  CS-
                shall  use  Table  R602.10.3(1)  and  the  applicable   WSP, CS-G and CS-PF along a braced wall line
                adjustment factors in Table R602.10.3(2).               shall  be  permitted.  Intermittent  methods  ABW,
              2. Detached buildings  in  Seismic Design Category  C     PFH and PFG shall be permitted to be used along
                shall  use  Table  R602.10.3(1)  and  the  applicable   a  braced wall line  with  continuous  sheathed
                adjustment factors in Table R602.10.3(2).               methods,  provided  that  the  length  of  required
                                                                        bracing for that braced wall line is determined in
              3. Townhouses in Seismic Design Category C shall use
                the  greater  value  determined  from  Table            accord           Tabl    R602.10.3(   or
                R602.10.3(1)  or  R602.10.3(3)  and  the  applicable    R602.10.3(3) using the highest value of the brac-
                adjustment  factors  in  Table  R602.10.3(2)  or        ing methods used.
                R602.10.3(4), respectively.                          5. In Seismic Design Categories A and B, and for
                                                                        detached one- and two-family dwellings in Seis-
              4. All buildings in Seismic Design Categories D , D 1
                                                      0
                and D  shall use the greater value determined from      mic  Design  Category  C,  mixing  of  intermittent
                     2
                Table R602.10.3(1) or R602.10.3(3) and the appli-       bracing  methods  along  the  interior  portion  of  a
                cable  adjustment  factors  in  Table  R602.10.3(2)  or  braced wall line with continuous sheathing meth-
                R602.10.3(4), respectively.                             ods CS-WSP, CS-G and CS-PF along the exterior
                                                                        portion of the same braced wall line shall be per-
              Only braced wall panels parallel to the braced wall line  mitted.  The  length  of  required  bracing  shall  be
           shall contribute toward the required length of bracing of    the highest value of all intermittent bracing meth-
           that braced wall line. Braced wall panels along an angled    ods used in accordance with Table R602.10.3(1)
           wall meeting the minimum length requirements of Tables       or  R602.10.3(3)  as  adjusted  by  Tables
           R602.10.5 and R602.10.5.2 shall be permitted to contrib-     R602.10.3(2) and R602.10.3(4), respectively. The
           ute  its  projected  length  toward  the  minimum  required  requirements of Section R602.10.7 shall apply to
           length of bracing for the braced wall line as shown in Fig-  each end of the continuously sheathed portion of
           ure R602.10.1.4. Any braced wall panel on an angled wall     the braced wall line.


         194                                                                 2018 INTERNATIONAL RESIDENTIAL CODE  ®