WALL CONSTRUCTION



                  R608.5.4.2  Location of  reinforcement in  walls.  For  located in the middle third of the span between lateral sup-
                  location  of  reinforcement  in  foundation  walls  and  ports, or located and constructed as required for joints in
                  above-grade  walls,  see  Sections  R404.1.3.3.7.2  and  plain concrete walls.
                  R608.6.5, respectively.                              Exception:  Vertical  wall  reinforcement  required  by
                  R608.5.4.3  Lap  splices.  Vertical  and  horizontal  wall  this code is permitted to be used in lieu of construction
                  reinforcement required by Sections R608.6 and R608.7  joint  reinforcement,  provided  the  spacing  does  not
                  shall be the longest lengths practical. Where splices are  exceed 24 inches (610 mm), or the combination of wall
                  necessary  in  reinforcement,  the  length  of  lap  splices  reinforcement  and  No.  4  bars  described  in  Section
                  shall be in accordance with Table R608.5.4(1) and Fig-  R608.5.5 does not exceed 24 inches (610 mm).
                  ure R608.5.4(1). The maximum gap between noncon-  R608.6 Above-grade wall requirements.
                  tact  parallel  bars  at  a  lap  splice  shall  not  exceed  the
                  smaller of one-fifth the required lap length and 6 inches  R608.6.1 General. The minimum thickness of load-bear-
                  (152 mm). See Figure R608.5.4(1).                  ing and nonload-bearing above-grade walls and reinforce-
                                                                     ment shall be as set forth in the appropriate table in this
                  R608.5.4.4  Development  of  bars  in  tension.  Where  section based on the type of wall form to be used. The wall
                  bars are required to be developed in tension by other  shall be designed in accordance with ACI 318 where the
                  provisions of this code, development lengths and cover  wall  or  building  is  not  within  the  limitations  of  Section
                  for hooks and bar extensions shall comply with Table  R608.2, where design is required by the tables in this sec-
                  R608.5.4(1) and Figure R608.5.4(2). The development  tion or where the wall is not within the scope of the tables
                  lengths shown in Table R608.5.4(1) shall apply to bun-  in this section.
                  dled bars in lintels installed in accordance with Section
                  R608.8.2.2.                                          Above-grade  concrete  walls  shall  be  constructed  in
                                                                     accordance  with  this  section  and  Figure  R608.6(1),
                  R608.5.4.5  Standard  hooks.  Where  reinforcement  is  R608.6(2), R608.6(3) or R608.6(4). Above-grade concrete
                  required by this code to terminate with a standard hook,  walls that are continuous with stem walls and not laterally
                  the hook shall comply with Figure R608.5.4(3).     supported  by  the  slab-on-ground  shall  be  designed  and
                  R608.5.4.6 Webs of waffle-grid walls. Reinforcement,  constructed  in  accordance  with  this  section.  Concrete
                  including stirrups, shall not be placed in webs of waf-  walls shall be supported on continuous foundation walls or
                  fle-grid walls, including lintels. Webs are permitted to  slabs-on-ground  that  are  monolithic  with  the  footing  in
                  have form ties.                                    accordance  with  Section  R403.  The  minimum  length  of
                                                                     solid  wall without openings shall  be in accordance with
                  R608.5.4.7  Alternate  grade  of  reinforcement  and
                  spacing.  Where  tables  in  Sections  R404.1.3  and  Section R608.7. Reinforcement around openings, includ-
                  R608.6  specify  vertical  wall  reinforcement  based  on  ing  lintels,  shall  be  in  accordance  with  Section  R608.8.
                  minimum  bar  size  and  maximum  spacing,  which  are  Lateral support for above-grade walls in the out-of-plane
                  based on Grade 60 (420 MPa) steel reinforcement, dif-  direction  shall  be  provided  by  connections  to  the  floor
                  ferent size bars or bars made from a different grade of  framing  system,  if  applicable,  and  to  ceiling  and  roof
                  steel are permitted provided an equivalent area of steel  framing systems in accordance with Section R608.9. The
                  per  linear  foot  of  wall  is  provided.  Use  of  Table  wall thickness shall be equal to or greater than the thick-
                  R608.5.4(2)  is  permitted  to  determine  the  maximum  ness of the wall in the story above.
                  bar spacing for different bar sizes than specified in the  R608.6.2  Wall  reinforcement  for  wind.  Vertical  wall
                  tables  and bars  made  from a  different grade  of  steel.  reinforcement  for  resistance  to  out-of-plane  wind  forces
                  Bars  shall  not  be  spaced  less  than  one-half  the  wall  shall  be  determined  from  Table  R608.6(1),  R608.6(2),
                  thickness, or more than 48 inches (1219 mm) on center.  R608.6(3) or R608.6(4). For the design of nonload-bear-
               R608.5.5  Construction  joints  in  walls.  Construction  ing walls, in Tables R608.6(1), R608.6(2) and R608.6(3)
               joints shall be made and located to not impair the strength  use the appropriate column labeled “Top.” (see Sections
               of  the  wall.  Construction  joints  in  plain  concrete  walls,  R608.7.2.2.2 and R608.7.2.2.3). There shall be a vertical
               including walls required to have not less than No. 4 bars at  bar  at  corners  of  exterior  walls.  Unless  more  horizontal
               48 inches (1219 mm) on center by Section R608.6, shall  reinforcement  is  required  by  Section  R608.7.2.2.1,  the
               be located at points of lateral support, and not less than  minimum  horizontal  reinforcement  shall  be  four  No.  4
               one No. 4 bar shall extend across the construction joint at a  bars  [Grade  40  (280  MPa)]  placed  as  follows:  top  bar
               spacing not to exceed 24 inches (610 mm) on center. Con-  within 12 inches (305 mm) of the top of the wall, bottom
               struction joint reinforcement  shall have not less  than 12  bar within 12 inches (305 mm) of the finish floor and one
               inches (305 mm) of embedment on both sides of the joint.  bar each at approximately one-third and two-thirds of the
               Construction joints  in reinforced  concrete walls shall be  wall height.