Page 433 - 2018_IRC
P. 433

ROOF-CEILING CONSTRUCTION



                                DEPTH OF TAPER
                                CUT, D/4 MAX.
                                MEASURED AT
                                INSIDE FACE
                                OF SUPPORT
                                                                                    DEPTH, D
                                                     JOIST DEPTH AT
                                                     TAPER CUT





















                                                     FIGURE R802.7.1.2
                                                  CEILING JOIST TAPER CUT
         ters  with  ceiling  joists  attached  in  accordance  with  Table  installation. Truss design drawings shall be provided with
         R602.3(1), the depth-to-thickness ratio for the total assembly  the  shipment  of  trusses  delivered  to  the  job  site.  Truss
         shall be determined using the combined thickness of the raf-  design drawings shall include, at a minimum, the follow-
         ter plus the attached ceiling joist.                    ing information:
           Exception:  Roof  trusses  shall  be  braced  in  accordance  1. Slope or depth, span and spacing.
           with Section R802.10.3.                                 2. Location of all joints.
           R802.8.1  Bridging.  Rafters  and  ceiling  joists  having  a  3. Required bearing widths.
           depth-to-thickness ratio exceeding 6 to 1 based on nominal
           dimensions shall be supported laterally by solid blocking,  4. Design loads as applicable.
           diagonal bridging (wood or metal) or a continuous 1-inch     4.1. Top  chord  live  load  (as  determined  from
           by 3-inch (25 mm by 76 mm) wood strip nailed across the          Section R301.6).
           rafters  or  ceiling  joists  at  intervals  not  exceeding  8  feet  4.2. Top chord dead load.
           (2438 mm).
                                                                        4.3. Bottom chord live load.
         R802.9 Framing of openings. Openings in roof and ceiling
         framing shall be framed with header and trimmer joists. Where  4.4. Bottom chord dead load.
         the header joist span does not exceed 4 feet (1219 mm), the    4.5. Concentrated loads and their points of appli-
         header joist shall be permitted to be a single member the same     cation.
         size as the ceiling joist or rafter. Single trimmer joists shall be  4.6. Controlling wind and earthquake loads.
         permitted to be used to carry a single header joist that is located  5. Adjustments  to  lumber  and  joint  connector  design
         within 3 feet (914 mm) of the trimmer joist bearing. Where the  values for conditions of use.
         header joist span exceeds 4 feet (1219 mm), the trimmer joists
         and the header joist shall be doubled and of sufficient cross  6. Each reaction force and direction.
         section to support the ceiling joists or rafter framing into the  7. Joint  connector  type  and  description  such  as  size,
         header. Approved hangers shall be used for the header joist to  thickness or gage and the dimensioned location of
         trimmer joist connections where the header joist span exceeds  each  joint  connector  except  where  symmetrically
         6 feet (1829 mm). Tail joists over 12 feet (3658 mm) long shall  located relative to the joint interface.
         be supported at the header by framing anchors or on ledger
         strips not less than 2 inches by 2 inches (51 mm by 51 mm).  8. Lumber size, species and grade for each member.
                                                                   9. Connection requirements for:
         R802.10 Wood trusses.
                                                                        9.1. Truss to girder-truss.
           R802.10.1  Truss  design  drawings.  Truss  design  draw-
           ings, prepared in conformance to Section R802.10.1, shall    9.2. Truss ply to ply.
           be provided to the building official and approved prior to   9.3. Field splices.