ENERGY EFFICIENCY



           by  an  accredited,  independent  laboratory  and  listed  and  manufacturer  with  a  heating  temperature  setpoint  of  not
           labeled by the manufacturer.                          greater than 70°F (21°C) and a cooling temperature setpoint
              Exception: Site-built windows, skylights and doors.  of not less than 78°F (26°C).
           N1102.4.4  (R402.4.4)  Rooms  containing  fuel-burning  N1103.1.2  (R403.1.2)  Heat  pump  supplementary heat
           appliances.  In  Climate Zones  3  through  8,  where  open  (Mandatory). Heat pumps having supplementary electric-
           combustion air ducts provide combustion air to open com-  resistance  heat  shall  have  controls  that,  except  during
           bustion fuel-burning appliances, the appliances and com-  defrost,  prevent  supplemental  heat  operation  when  the
           bustion air opening shall be located outside the building  heat pump compressor can meet the heating load.
           thermal envelope  or  enclosed  in  a  room  that  is  isolated  N1103.2 (R403.2) Hot water boiler outdoor temperature
           from  inside  the  thermal  envelope.  Such  rooms  shall  be  setback. Hot water boilers that supply heat to the building
           sealed  and  insulated  in  accordance  with  the  envelope  through one- or two-pipe heating systems shall have an out-
           requirements of Table N1102.1.2, where the walls, floors  door setback control that decreases the boiler water tempera-
           and ceilings shall meet a minimum of the basement wall  ture based on the outdoor temperature.
           R-value requirement. The door into the room shall be fully
           gasketed and any water lines and ducts in the room insu-  N1103.3  (R403.3)  Ducts.  Ducts  and  air  handlers  shall  be
           lated in accordance with Section N1103. The combustion  installed  in  accordance  with  Sections  N1103.3.1  through
                                                              N1103.3.8.
           air duct shall be insulated where it passes through condi-
           tioned space to an R-value of not less than R-8.      N1103.3.1 (R403.3.1) Insulation (Prescriptive). Supply
                                                                 and return ducts in attics shall be insulated to an R-value
              Exceptions:
                                                                 of not less than R-8 for ducts 3 inches (76 mm) in diameter
                1. Direct  vent  appliances  with  both  intake  and  and larger and not less than R-6 for ducts smaller than 3
                   exhaust pipes installed continuous to the outside.  inches (76 mm) in diameter. Supply and return ducts in
                                                                 other portions of the building shall be insulated to not less
                2. Fireplaces  and  stoves  complying  with  Sections
                   N1102.4.2 and R1006.                          than R-6 for ducts 3 inches (76 mm) in diameter and to not
                                                                 less than R-4.2 for ducts smaller than 3 inches (76.2 mm)
           N1102.4.5 (R402.4.5) Recessed lighting. Recessed lumi-  in diameter.
           naires  installed  in  the building thermal envelope  shall  be  Exception:  Ducts  or  portions  thereof  located  com-
           sealed to limit air leakage between conditioned and uncon-
           ditioned spaces. Recessed luminaires shall be IC-rated and  pletely inside the building thermal envelope.
           labeled as having an air leakage rate of not greater than 2.0  N1103.3.2  (R403.3.2)  Sealing  (Mandatory).  Ducts,  air
           cfm  (0.944  L/s)  when  tested  in  accordance  with  ASTM  handlers and filter boxes shall be sealed. Joints and seams
           E283 at a pressure differential of 1.57 psf (75 Pa). Recessed  shall comply with Section M1601.4.1.
           luminaires shall be sealed with a gasket or caulked between  N1103.3.2.1 (R403.3.2.1) Sealed air handler. Air han-
           the housing and the interior wall or ceiling covering.
                                                                   dlers shall have a manufacturer’s designation for an air
         N1102.5  (R402.5)  Maximum  fenestration  U-factor  and   leakage of not greater than 2 percent of the design air-
         SHGC (Mandatory). The area-weighted average maximum       flow rate when tested in accordance with ASHRAE 193.
         fenestration U-factor permitted using tradeoffs from Section  N1103.3.3 (R403.3.3) Duct testing (Mandatory). Ducts
         N1102.1.5 or N1105 shall be 0.48 in Climate Zones 4 and 5  shall be pressure tested to determine air leakage by one of
         and 0.40 in Climate Zones 6 through 8 for vertical fenestra-  the following methods:
         tion, and 0.75 in Climate Zones 4 through 8 for skylights. The
         area-weighted average maximum fenestration SHGC permit-   1. Rough-in test: Total leakage shall be measured with a
         ted using tradeoffs from Section N1105 in Climate Zones 1   pressure differential of 0.1 inch w.g. (25 Pa) across
         through 3 shall be 0.50.                                    the system, including the manufacturer’s air handler
                                                                     enclosure if installed at the time of the test. Registers
                                                                     shall be taped or otherwise sealed during the test.
                       SECTION N1103 (R403)
                             SYSTEMS                               2. Postconstruction  test:  Total  leakage  shall  be  mea-
                                                                     sured  with  a  pressure  differential  of  0.1  inch  w.g.
         N1103.1 (R403.1) Controls (Mandatory). Not less than one    (25 Pa) across the entire system, including the man-
         thermostat  shall  be  provided  for  each  separate  heating  and  ufacturer’s air handler enclosure. Registers shall be
         cooling system.                                             taped or otherwise sealed during the test.
           N1103.1.1  (R403.1.1)  Programmable  thermostat.  The   Exceptions:
           thermostat controlling the primary heating or cooling sys-
           tem of the dwelling unit shall be capable of controlling the  1. A  duct  air-leakage  test  shall  not  be  required
           heating and cooling system on a daily schedule to maintain   where  the  ducts  and  air  handlers  are  located
           different temperature set points at different times of the day.  entirely within the building thermal envelope.
           This thermostat shall include the capability to set back or  2. A duct air-leakage test shall not be required for
           temporarily operate the system to maintain zone tempera-     ducts serving heat or energy recovery ventilators
           tures of not less than 55°F (13°C) to not greater than 85°F  that are not integrated with ducts serving heating
           (29°C). The thermostat shall be programmed initially by the  or cooling systems.