Page 850 - 2018_IRC
P. 850

APPENDIX A



             meter to the farthest remote appliance is only used to size the  adequate  for  the  calculated  gas  load  and  that  the
             initial parts of the overall piping system. The Branch Length  required pressure drop (across the regulator) for that
                                                                                             3
             Method is applied in the following manner:                 capacity does not exceed  /  psi (5.2 kPa) for a 2 psi
                                                                                              4
               (1) Determine  the  gas  load  for  each  of  the  connected  (13.8 kPa) system. If the pressure drop across the reg-
                   appliances.                                          ulator is too high (for the connected gas load), select a
               (2) Starting from the meter, divide the piping system into  larger regulator.
                   a number of connected segments, and determine the  (2) Measure the distance from the meter to the line regu-
                   length  and  amount  of  gas  that  each  segment  would  lator located inside the building.
                   carry  assuming  that  all  appliances  were  operated  (3) If there are multiple line regulators, measure the dis-
                   simultaneously. An allowance (in equivalent length of  tance from the meter to the regulator farthest removed
                   pipe) as determined from Table A.2.2 should be con-  from the meter.
                   sidered for piping segments that include four or more  (4) The maximum allowable pressure drop for the 2 psi
                   fittings.                                            (13.8 kPa) section is 1 psi (6.9 kPa).
               (3) Determine  the  distance  from  the  outlet  of  the  gas  (5) Referring  to  the  appropriate  sizing  table  (based  on
                   meter  to  the  appliance  farthest  removed  from  the  piping material) for 2 psi (13.8 kPa) systems with a 1
                   meter.                                               psi (6.9 kPa) pressure drop, find this distance in the
               (4) Using the longest distance (found in Step 3), size each  first column, or the closest larger distance if the exact
                   piping  segment  from  the  meter  to  the  most  remote  distance is not listed.
                   appliance outlet.                                 (6) Trace across this row until the gas load is found or the
               (5) For  each  of  these  piping  segments,  use  the  longest  closest  larger  capacity  if  the  exact  capacity  is  not
                   length and the calculated gas load for all of the con-  listed.
                   nected appliances for the segment and begin the siz-  (7) Read up the table column to the top row and select the
                   ing process in Steps 6 through 8.                    appropriate pipe size.
               (6) Referring  to  the  appropriate  sizing  table  (based  on  (8) If there are multiple regulators in this portion of the
                   operating  conditions  and  piping  material),  find  the  piping system, each line segment must be sized for its
                   longest length distance in the first column or the next  actual  gas  load,  but  using  the  longest  length  previ-
                   larger distance if the exact distance is not listed. The  ously determined in steps 2 and 3.
                   use  of  alternative  operating  pressures  or  pressure
                   drops will require the use of a different sizing table,  The  low  pressure  section  (all  piping  downstream  of  the
                   but  will  not  alter  the  sizing  methodology.  In  many  line regulator) is sized as follows:
                   cases,  the  use  of  alternative  operating  pressures  or  (1) Determine  the  gas  load  for  each  of  the  connected
                   pressure drops will require the approval of both the  appliances.
                   code official and the local gas serving utility.  (2) Starting from the line regulator, divide the piping sys-
               (7) Trace across this row until the gas load is found or the  tem into a number of connected segments or indepen-
                   closest  larger  capacity  if  the  exact  capacity  is  not  dent  parallel  piping  segments,  and  determine  the
                   listed.                                              amount of gas that each segment would carry assum-
                                                                        ing that all appliances were operated simultaneously.
               (8) Read up the table column and select the appropriate
                   pipe size in the top row. Repeat Steps 6, 7 and 8 for  An allowance (in equivalent length of pipe) as deter-
                   each pipe segment in the longest run.                mined from Table A.2.2 should be considered for pip-
                                                                        ing segments that include four or more fittings.
               (9) Size each remaining section of branch piping not pre-
                   viously sized by measuring the distance from the gas  (3) For each piping segment, use the actual length or lon-
                   meter  location  to  the  most  remote  outlet  in  that  gest length (if there are sub-branchlines) and the cal-
                   branch, using the gas load of attached appliances and  culated gas load for that segment and begin the sizing
                   following the procedures of Steps 2 through 8.       process as follows:
                                                                           (a) Referring to the appropriate sizing table (based
             A.3.3 Hybrid pressure method. The sizing of a 2 psi (13.8        on  operating  pressure  and  piping  material),
             kPa)  gas  piping  system  is  performed  using  the  traditional  find the longest length distance in the first col-
             Longest  Length  Method  but  with  modifications.  The  2  psi  umn or the closest larger distance if the exact
             (13.8  kPa)  system  consists  of  two  independent  pressure    distance  is  not  listed.  The  use  of  alternative
             zones, and each zone is sized separately. The Hybrid Pressure    operating  pressures  or  pressure  drops  will
             Method is applied as follows:                                    require the use of a different sizing table, but
               The sizing of the 2 psi (13.8 kPa) section (from the meter     will not alter the sizing methodology. In many
             to the line regulator) is as follows:                            cases, the use of alternative operating pressures
               (1) Calculate the gas load (by adding up the name plate        or pressure drops can require the approval of
                   ratings) from all connected appliances. (In certain cir-   the code official.
                   cumstances the installed gas load can be increased up   (b) Trace  across  this  row  until the  appliance  gas
                   to  50  percent  to  accommodate  future  addition  of     load is found or the closest larger capacity if
                   appliances.) Ensure that the line regulator capacity is    the exact capacity is not listed.

             2018 INTERNATIONAL RESIDENTIAL CODE ®                                                               825
  Copyrighted © 2017 by, or licensed to, ICC (ALL RIGHTS RESERVED); licensed to UL, LLC pursuant to License Agreement with ICC. No further reproductions authorized or distribution authorized.
  ANY UNAUTHROIZED REPRODUCTION OR DISTRIBUTION IS A VIOLATION OF THE FEDERAL COPYRIGHT ACT AND THE LICENSE AGREEMENT; AND SUBJECT TO CIVIL AND CRIMINAL PENALTIES THEREUNDER.
   845   846   847   848   849   850   851   852   853   854   855