APPENDIX K

                                              SOUND TRANSMISSION




                 The provisions contained in this appendix are not mandatory unless specifically referenced in the adopting ordinance.
             User note:
                About this appendx: Sound transmission relates directly to the psychological and long-term physical well-being of building occupants. Many
                human activities cannot be accommodated efficiently or comfortably in various types of building spaces without proper attention to the mitiga-
                tion of sound transmission from other spaces within the building, or from outside of the building. In Appendix K, attention is specifically paid to
                the mitigation of sound transmission between dwelling units and other dwelling units and occupancies.



                              SECTION AK101                                        SECTION AK103
                                 GENERAL                                    STRUCTURAL-BORNE SOUND
             AK101.1 General. Wall and floor-ceiling assemblies sepa-
             rating  dwelling units,  including  those  separating  adjacent  AK103.1 General. Floor/ceiling assemblies between dwell-
                                                                  ing units, or between a dwelling unit and a public or service
             townhouse units, shall provide airborne sound insulation for  area within a structure, shall have an impact insulation class
             walls,  and  both  airborne  and  impact  sound  insulation  for  (IIC)  rating  of  not  less  than  45  when  tested  in  accordance
             floor-ceiling assemblies.                            with ASTM E492.


                              SECTION AK102
                            AIRBORNE SOUND                                         SECTION AK104
             AK102.1  General.  Airborne  sound  insulation  for  wall  and  REFERENCED STANDARDS
             floor-ceiling assemblies shall meet a sound transmission class  ASTM E90—09  Test Method for Laboratory  AK102.1
             (STC) rating of  45  when  tested in  accordance  with ASTM           Measurement of Airborne   AK102.1.1
             E90. Penetrations or openings in construction assemblies for          Sound Transmission Loss of
             piping; electrical devices; recessed cabinets; bathtubs; soffits;     Building Partitions and Elements
             or heating, ventilating or exhaust ducts shall be sealed, lined,  ASTM E492—09  Specification for Laboratory  AK103.1
             insulated  or  otherwise  treated  to  maintain  the  required  rat-  Measurement of Impact Sound
             ings. Dwelling unit entrance doors, which share a common              Transmission through Floor-ceiling
             space, shall be tight fitting to the frame and sill.                  Assemblies Using the Tapping
               AK102.1.1  Masonry.  The  sound  transmission  class  of            Machine
               concrete  masonry  and  clay  masonry  assemblies  shall  be  TMS 0302—12  Standard for Determining  AK102.1.1
               calculated  in  accordance  with  TMS  0302  or  determined         the Sound Transmission Class
               through testing in accordance with ASTM E90.                        Rating for Masonry Walls





























             2018 INTERNATIONAL RESIDENTIAL CODE ®                                                               887